| Plan Review Notes For Permit 11120483 |
| Permit Number |
11120483 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2012-02-15 10:19:13 | 6501 NORTH JOG ROAD | | | PERMIT #11120483 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | I HAVE SOME MAJOR CONCERNS WITH THE WATER MAIN | | | SUPPLYING THE COMBINED DEMAND OF THE FIRE HYDRANTS AND | | | DOMESTIC WATER: | | | 1) THE FEED TO THE REMOTE FIRE HYDRANT RESULTS IN A | | | DEAD-END MAIN. | | | 2) THE 6-INCH WATER MAIN WOULD SEEM TO BE UNDERSIZED IN | | | SUPPLYING COMBINED FIRE DEMAND AND DOMESTIC DEMAND. | | | 3) THE DOMESTIC WATER PVC PIPE IN THE TRAILERS COULD | | | BECOME DESTROYED IN A FIRE EVENT AND COMPROMISE THE | | | MUCH NEEDED FLOW AND PRESSURE FOR FIRE SUPPRESSION | | | OPERATIONS. | | | | | | I WOULD PREFER TO HAVE THE FIRE MAIN COMPLETELY | | | SEPARATED FROM THE DOMESTIC WATER. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW |
|