| 2011-12-28 15:46:07 | BUILDING PLAN REVIEW |
| | PERMIT: 11120478 |
| | ADD: 3111 S DIXIE HWY |
| | CONT: FISHER CONTRACTING CORP |
| | TEL: (561)691-4716 |
| | |
| | 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PERMIT APPLICATION INDICATES THE PERMIT VALUE OF |
| | $122,000. THE FLORIDA ACCESIBILITY CODE UNDER |
| | 11-4.1.6(2) (2) ALTERATIONS TO AN AREA CONTAINING A |
| | PRIMARY FUNCTION. IN ADDITION TO THE REQUIREMENTS OF |
| | SECTION 11-4.1.6(1), AN ALTERATION THAT AFFECTS OR |
| | COULD AFFECT THE USABILITY OF OR ACCESS TO AN AREA |
| | CONTAINING A PRIMARY FUNCTION SHALL BE MADE SO AS TO |
| | ENSURE THAT, TO THE MAXIMUM EXTENT FEASIBLE, THE PATH |
| | OF TRAVEL TO THE ALTERED AREA AND THE RESTROOMS, |
| | TELEPHONES, AND DRINKING FOUNTAINS SERVING THE ALTERED |
| | AREA, ARE READILY ACCESSIBLE TO AND USABLE BY |
| | INDIVIDUALS WITH DISABILITIES, UNLESS SUCH ALTERATIONS |
| | ARE DISPROPORTIONATE TO THE OVERALL ALTERATIONS TIN |
| | TERMS OF COST AND SCOPE. |
| | |
| | ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF |
| | TRAVEL TO ALTERED AREAS SHALL BE DEEMED |
| | DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE |
| | COST EXCEEDS 20 PERCENT OF THE COST OF THE ALTERATION |
| | TO THE PRIMARY FUNCTION AREA. |
| | |
| | DUTY TO PROVIDE ACCESSIBLE FEATURES IN THE EVENT OF |
| | DISPROPORTIONALITY. |
| | |
| | 11-4.1.6(2)(1) WHEN THE COST OF ALTERATIONS NECESSARY |
| | TO MAKE THE PATH OF TRAVEL TO THE ALTERED AREA FULLY |
| | ACCESSIBLE IS DISPROPORTIONATE TO THE COST OF THE |
| | OVERALL ALTERATION, THE PATH OF TRAVEL SHALL BE MADE |
| | ACCESSIBLE TO THE EXTENT THAT IT CAN BE MADE ACCESSIBLE |
| | WITHOUT INCURRING DISPROPORTIONATE COSTS. |
| | |
| | (2)(A) IN CHOOSING WHICH ACCESSIBLE ELEMENTS TO |
| | PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE ELEMENTS |
| | THAT WILL PROVIDE THE GREATEST ACCESS, IN THE FOLLOWING |
| | ORDER: |
| | |
| | (I) AN ACCESSIBLE ENTRANCE; |
| | |
| | (II) AN ACCESSIBLE ROUTE TO THE ALTERED AREA: |
| | |
| | (III) AT LEAST ONE ACCESSIBLE RESTROOM FOR EACH SEX OR |
| | A SINGLE UNISEX RESTROOM: |
| | |
| | (IV) ACCESSIBLE TELEPHONES; |
| | |
| | (V) ACCESSIBLE DRINKING FOUNTAINS; |
| | |
| | |
| | 1A) THE DISPROPORTIONATE COST ALLOWS FOR $24,400 IN |
| | MAKING THIS TENANT SPACE ACCESSIBLE. DOOR 103 DOES NOT |
| | HAVE THE 18 INCHES ON THE LATCH SIDE OFTHE DOOR. |
| | |
| | 1B) IT IS NOT CLEAR AS TO WHICH OF THE RESTROOMS ARE TO |
| | BE THE ACCESSBILE RESTROOM |
| | |
| | 1C) OPEN OFFICE SPACE FOUND ON SHEET A-1.0 & A-1.1 BOTH |
| | APPEAR TO HAVE A RAISED FLOOR DECK BUT NO VERTICAL |
| | ACCESSIBILITY (RAMPS) TO GAIN ACCESS. |
| | PLEASE REVIEW 11-4.8 RAMP REQUIREMENTS. |
| | |
| | 2) DOOR # 103 SWINGS THE WRONG WAY FOR EGRESS WITH AN |
| | OCCUPANT LOAD OF 50 OR GREATER. FBC-B 1008.1.2. |
| | |
| | 3) RAISED FLOORING SHEETS A-1.0, A-1.1 & A-3.0 DETAILS |
| | 9 & 10 1003.5.2 . WHERE RAMPS ARE REQUIRED. |
| | |
| | JAMES A. WITMER CBO |