2012-01-03 14:40:072007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) SECTION 606.4 OF THE EXISTING BUILDING CODE REQUIRES
 OPENING PROTECTION FOR GLAZED OPENINGS WHEN MORE THAN
 25 PERCENT OF THE AGGREGATE GLAZED AREA IS REPLACED.
 THE WINDOW AND DOOR SCHEDULE INDICATES THAT THERE ARE
 19 GLAZED OPENINGS AND UNDER A PREVIOUS PERMIT STORM
 PANELS WERE INSTALLED ON 16 OPENINGS. PLEASE SUBMIT
 PRODUCT APPROVALS AND INSTALLATION SCHEDULES FOR STORM
 PANELS FOR ADDITIONAL GLAZED OPENINGS.
  
 2) TWO PRODUCT APPROVALS WERE SUBMITTED FOR THE FLAT
 ROOF. ONE IS FOR A CONVENTIONAL BUILT-UP ROOF AND THE
 OTHER IS FOR A MODIFIED BITUMEN ROOF. PLEASE INDICATE
 WHICH ONE WILL BE INSTALLED AND SPECIFY THE APPROVED
 ASSEMBLY, FASTENING OPTION AND DESIGN PRESSURE FOR IT.
 SUBMIT TWO COPIES OF SIGNED AND SEALED RAS 117
 CALCULATIONS FOR ENHANCED FASTENING THAT WILL BE
 REQUIRED TO MEET THE HIGHER UPLIFT REQUIREMENTS AT THE
 PERIMETER AND CORNER AREAS OF THE ROOF. SEE LIMITATION
 NUMBER 7 OF THE PRODUCT APPROVAL.
  
 3) SUBMIT TWO COPIES OF THE INSTALLATION INSTRUCTIONS
 AND A FLORIDA PRODUCT APPROVAL COVERSHEET WITH THE FL #
 FOR THE SINGLE ENTRY DOORS AS REQUIRED BY DCA RULE
 9N-3.
  
 4) SUBMIT TWO COPIES OF AN EXISTING AND PROPOSED FLOOR
 PLAN FOR THE KITCHEN CABINETS. CITY AMENDMENTS 106.1.1
  