2014-02-10 12:07:15****CORRECTIONS****
 ****BASED ON ELEVATION CERTIFICATE PREPARED BY MARK D.
 LAING DATED 1/28/14 AND PLANS ON FILE***
 ****3RD REVIEW (SOME COMMENTS REVISED)****
  
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 CFM US-12-06546
 561-805-6724
 [email protected]
  
 1. OK
  
 2. A9 (B) STATES THAT THREE PERMANENT FLOOD OPENINGS
 WITHIN 1' ABOVE ADJACENT GRADE WERE INSTALLED. PLAN
 SHOWS THAT FOUR ARE REQUIRED. REVISE A-1. SUBMIT THE
 ICC EVALUATION REPORT FOR THE ENGINEERED VENTS WHICH
 WERE INSTALLED.
  
 3. N/A
  
 4. EC STATES IN A9(C) THAT THERE ARE 376 SQUARE INCHES
 OF NET AREA FLOOD OPENINGS. IT ALSO STATES THAT THREE
 ARE INSTALLED, AND THE EVALUATION REPORT FOR SMARTVENT
 1540-510 STATES THAT EACH VENT YIELDS 51 SQUARE INCHES
 PER VENT FOR VENTILATION. PROVIDE CALCULATIONS OR
 REVISE. NOTE THAT THIS IS TO BE NET AREA.
  
 5-9. OK
  
  
  
  
 INSPECTOR TO VERIFY THE FOLLOWING (ITEMS SUBJECT TO
 CHANGE PURSUANT TO SUBMITTAL OF REVISION OR ADDITIONAL
 INFORMATION) :
  
 NO DRYWALL TO BE INSTALLED (IN GARAGE) BELOW 7'6", SEE
 (REVISED) SHEET A-1. BASED ON THE ELEVATION
 CERTIFICATE, NO DRYWALL ALLOWED FROM SLAB TO 1'4" ABOVE
 GARAGE SLAB.
  
 FLOOD VENT INSTALLATION ON PLAN (SEE REVISION
 #12060640, REVISED SHEET A1 DATED 4/9/12) SHOWS TWO
 FLOOD VENTS ON EACH EXTERIOR SIDE OF GARAGE; VERIFY
 INSTALLATION LOCATIONS. (NOTE CONFLICT WITH EC, SEE
 ITEM 2)
  
 FLOOD VENT HAS LABEL BEARING THE MANUFACTURER'S NAME
 (SMARTVENT PRODUCTS, INC.), THE MODEL NUMBER (1540-510)
 AND THE EVALUATION REPORT NUMBER (ESR-2074).
  
  
  
  
  
  
  