| 2014-02-10 12:07:15 | ****CORRECTIONS**** |
| | ****BASED ON ELEVATION CERTIFICATE PREPARED BY MARK D. |
| | LAING DATED 1/28/14 AND PLANS ON FILE*** |
| | ****3RD REVIEW (SOME COMMENTS REVISED)**** |
| | |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | CFM US-12-06546 |
| | 561-805-6724 |
| | [email protected] |
| | |
| | 1. OK |
| | |
| | 2. A9 (B) STATES THAT THREE PERMANENT FLOOD OPENINGS |
| | WITHIN 1' ABOVE ADJACENT GRADE WERE INSTALLED. PLAN |
| | SHOWS THAT FOUR ARE REQUIRED. REVISE A-1. SUBMIT THE |
| | ICC EVALUATION REPORT FOR THE ENGINEERED VENTS WHICH |
| | WERE INSTALLED. |
| | |
| | 3. N/A |
| | |
| | 4. EC STATES IN A9(C) THAT THERE ARE 376 SQUARE INCHES |
| | OF NET AREA FLOOD OPENINGS. IT ALSO STATES THAT THREE |
| | ARE INSTALLED, AND THE EVALUATION REPORT FOR SMARTVENT |
| | 1540-510 STATES THAT EACH VENT YIELDS 51 SQUARE INCHES |
| | PER VENT FOR VENTILATION. PROVIDE CALCULATIONS OR |
| | REVISE. NOTE THAT THIS IS TO BE NET AREA. |
| | |
| | 5-9. OK |
| | |
| | |
| | |
| | |
| | INSPECTOR TO VERIFY THE FOLLOWING (ITEMS SUBJECT TO |
| | CHANGE PURSUANT TO SUBMITTAL OF REVISION OR ADDITIONAL |
| | INFORMATION) : |
| | |
| | NO DRYWALL TO BE INSTALLED (IN GARAGE) BELOW 7'6", SEE |
| | (REVISED) SHEET A-1. BASED ON THE ELEVATION |
| | CERTIFICATE, NO DRYWALL ALLOWED FROM SLAB TO 1'4" ABOVE |
| | GARAGE SLAB. |
| | |
| | FLOOD VENT INSTALLATION ON PLAN (SEE REVISION |
| | #12060640, REVISED SHEET A1 DATED 4/9/12) SHOWS TWO |
| | FLOOD VENTS ON EACH EXTERIOR SIDE OF GARAGE; VERIFY |
| | INSTALLATION LOCATIONS. (NOTE CONFLICT WITH EC, SEE |
| | ITEM 2) |
| | |
| | FLOOD VENT HAS LABEL BEARING THE MANUFACTURER'S NAME |
| | (SMARTVENT PRODUCTS, INC.), THE MODEL NUMBER (1540-510) |
| | AND THE EVALUATION REPORT NUMBER (ESR-2074). |
| | |
| | |
| | |
| | |
| | |
| | |
| | |