Plan Review Notes
Plan Review Notes For Permit 11120399
Permit Number 11120399
Review Stop B
Sequence Number 3
Notes
Date Text
2014-01-05 12:45:34****CORRECTIONS****
 ****BASED ON ELEVATION CERTIFICATE PREPARED BY MARK D.
 LAING DATED 12/9/13 AND PLANS ON FILE***
  
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 CFM US-12-06546
 561-805-6724
 [email protected]
  
 1. SHEET A-1 SHOWS GARAGE AS 534 SF, BUT ELEVATION
 CERTIFICATE A9(A) STATES GARAGE IS 400 SF. PLEASE
 CORRELATE. NOTE THAT INSTRUCTIONS STATE TO TAKE
 MEASUREMENTS FROM THE OUTSIDE OF THE GARAGE.
  
 2. A9 (B) STATES THAT THREE PERMANENT FLOOD OPENINGS
 WITHIN 1' ABOVE ADJACENT GRADE WERE INSTALLED. PLAN
 SHOWS THAT FOUR ARE REQUIRED. REVISE A-1. SUBMIT THE
 ICC EVALUATION REPORT FOR THE ENGINEERED VENTS WHICH
 WERE INSTALLED.
  
 3. N/A
  
 4. EC STATES IN A9(C) THAT THERE ARE 376 SQUARE INCHES
 OF NET AREA FLOOD OPENINGS. IT ALSO STATES THAT THREE
 ARE INSTALLED, AND THE EVALUATION REPORT FOR SMARTVENT
 1540-510 STATES THAT EACH VENT YIELDS 51 SQUARE INCHES
 PER VENT FOR VENTILATION. PROVIDE CALCULATIONS OR
 REVISE. NOTE THAT THIS IS TO BE NET AREA.
  
 5. ITEM B6, FIRM INDEX DATE IS INCORRECT (SHOULD BE
 MARCH 1, 1979).
  
 6. ITEM B7, FIRM PANEL IS INCORRECT (SHOULD BE MARCH 1,
 1979).
  
 7. ITEM C2 (E), EQUIPMENT IS INSTALLED AT 6.5', MUST BE
 7.5' MINIMUM.
  
 8. IN COMMENTS, EQUIPMENT IS NOTED AS AIR CONDITIONER
 PAD. THIS "FINISHED CONSTRUCTION" ELEVATION CERTIFICATE
 IS TO BE DONE AFTER ALL EQUIPMENT AND FINAL GRADING HAS
 BEEN DONE, SEE INSTRUCTIONS.
  
 PROVIDE ELEVATIONS FOR THE FOLLOWING ITEMS:
  
 CONDENSING UNIT (NOT THE CONCRETE PAD)
 WATER HEATER LOCATED IN GARAGE
 AIR HANDLER LOCATED IN GARAGE
 ANY OTHER EQUIPMENT SERVICING THE BUILDING
  
 ALL ITEMS SHOULD BE NOTED IN "COMMENTS" SECTION
 INCLUDING LOCATION AND PLATFORM INFORMATION IF
 APPLICABLE, SEE EC INSTRUCTIONS.
  
 9. ITEM C2(H) STATES "N/A" BUT PLANS SHOW THREE SETS OF
 STAIRS, PLEASE CORRELATE.
  
 10. SECTION D, IF LAT/LONG PROVIDED BY A SURVEYOR,
 SOURCE OF INFORMATION TO BE NOTED IN COMMENTS SECTION,
 SEE INSTRUCTIONS.
  
  
 INSPECTOR TO VERIFY THE FOLLOWING (ITEMS SUBJECT TO
 CHANGE PURSUANT TO SUBMITTAL OF REVISION OR ADDITIONAL
 INFORMATION) :
  
 NO DRYWALL TO BE INSTALLED (IN GARAGE) BELOW 7'6", SEE
 (REVISED) SHEET A-1. BASED ON THE ELEVATION
 CERTIFICATE, NO DRYWALL ALLOWED FROM SLAB TO 1'4" ABOVE
 GARAGE SLAB.
  
 FLOOD VENT INSTALLATION ON PLAN (SEE REVISION
 #12060640, REVISED SHEET A1 DATED 4/9/12) SHOWS TWO
 FLOOD VENTS ON EACH EXTERIOR SIDE OF GARAGE; VERIFY
 INSTALLATION LOCATIONS. (NOTE CONFLICT WITH EC, SEE
 ITEM 2)
  
 FLOOD VENT HAS LABEL BEARING THE MANUFACTURER'S NAME
 (SMARTVENT PRODUCTS, INC.), THE MODEL NUMBER (1540-510)
 AND THE EVALUATION REPORT NUMBER (ESR-2074).
  
  
  
  
  
  
  