| Date |
Text |
| 2014-01-05 12:45:34 | ****CORRECTIONS**** |
| | ****BASED ON ELEVATION CERTIFICATE PREPARED BY MARK D. |
| | LAING DATED 12/9/13 AND PLANS ON FILE*** |
| | |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | CFM US-12-06546 |
| | 561-805-6724 |
| | [email protected] |
| | |
| | 1. SHEET A-1 SHOWS GARAGE AS 534 SF, BUT ELEVATION |
| | CERTIFICATE A9(A) STATES GARAGE IS 400 SF. PLEASE |
| | CORRELATE. NOTE THAT INSTRUCTIONS STATE TO TAKE |
| | MEASUREMENTS FROM THE OUTSIDE OF THE GARAGE. |
| | |
| | 2. A9 (B) STATES THAT THREE PERMANENT FLOOD OPENINGS |
| | WITHIN 1' ABOVE ADJACENT GRADE WERE INSTALLED. PLAN |
| | SHOWS THAT FOUR ARE REQUIRED. REVISE A-1. SUBMIT THE |
| | ICC EVALUATION REPORT FOR THE ENGINEERED VENTS WHICH |
| | WERE INSTALLED. |
| | |
| | 3. N/A |
| | |
| | 4. EC STATES IN A9(C) THAT THERE ARE 376 SQUARE INCHES |
| | OF NET AREA FLOOD OPENINGS. IT ALSO STATES THAT THREE |
| | ARE INSTALLED, AND THE EVALUATION REPORT FOR SMARTVENT |
| | 1540-510 STATES THAT EACH VENT YIELDS 51 SQUARE INCHES |
| | PER VENT FOR VENTILATION. PROVIDE CALCULATIONS OR |
| | REVISE. NOTE THAT THIS IS TO BE NET AREA. |
| | |
| | 5. ITEM B6, FIRM INDEX DATE IS INCORRECT (SHOULD BE |
| | MARCH 1, 1979). |
| | |
| | 6. ITEM B7, FIRM PANEL IS INCORRECT (SHOULD BE MARCH 1, |
| | 1979). |
| | |
| | 7. ITEM C2 (E), EQUIPMENT IS INSTALLED AT 6.5', MUST BE |
| | 7.5' MINIMUM. |
| | |
| | 8. IN COMMENTS, EQUIPMENT IS NOTED AS AIR CONDITIONER |
| | PAD. THIS "FINISHED CONSTRUCTION" ELEVATION CERTIFICATE |
| | IS TO BE DONE AFTER ALL EQUIPMENT AND FINAL GRADING HAS |
| | BEEN DONE, SEE INSTRUCTIONS. |
| | |
| | PROVIDE ELEVATIONS FOR THE FOLLOWING ITEMS: |
| | |
| | CONDENSING UNIT (NOT THE CONCRETE PAD) |
| | WATER HEATER LOCATED IN GARAGE |
| | AIR HANDLER LOCATED IN GARAGE |
| | ANY OTHER EQUIPMENT SERVICING THE BUILDING |
| | |
| | ALL ITEMS SHOULD BE NOTED IN "COMMENTS" SECTION |
| | INCLUDING LOCATION AND PLATFORM INFORMATION IF |
| | APPLICABLE, SEE EC INSTRUCTIONS. |
| | |
| | 9. ITEM C2(H) STATES "N/A" BUT PLANS SHOW THREE SETS OF |
| | STAIRS, PLEASE CORRELATE. |
| | |
| | 10. SECTION D, IF LAT/LONG PROVIDED BY A SURVEYOR, |
| | SOURCE OF INFORMATION TO BE NOTED IN COMMENTS SECTION, |
| | SEE INSTRUCTIONS. |
| | |
| | |
| | INSPECTOR TO VERIFY THE FOLLOWING (ITEMS SUBJECT TO |
| | CHANGE PURSUANT TO SUBMITTAL OF REVISION OR ADDITIONAL |
| | INFORMATION) : |
| | |
| | NO DRYWALL TO BE INSTALLED (IN GARAGE) BELOW 7'6", SEE |
| | (REVISED) SHEET A-1. BASED ON THE ELEVATION |
| | CERTIFICATE, NO DRYWALL ALLOWED FROM SLAB TO 1'4" ABOVE |
| | GARAGE SLAB. |
| | |
| | FLOOD VENT INSTALLATION ON PLAN (SEE REVISION |
| | #12060640, REVISED SHEET A1 DATED 4/9/12) SHOWS TWO |
| | FLOOD VENTS ON EACH EXTERIOR SIDE OF GARAGE; VERIFY |
| | INSTALLATION LOCATIONS. (NOTE CONFLICT WITH EC, SEE |
| | ITEM 2) |
| | |
| | FLOOD VENT HAS LABEL BEARING THE MANUFACTURER'S NAME |
| | (SMARTVENT PRODUCTS, INC.), THE MODEL NUMBER (1540-510) |
| | AND THE EVALUATION REPORT NUMBER (ESR-2074). |
| | |
| | |
| | |
| | |
| | |
| | |
| | |