| Plan Review Notes For Permit 11120399 |
| Permit Number |
11120399 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2012-05-21 15:43:35 | REVISION REQUIRED | | | | | | THE LAUNDRY ROOM IS A PROHIBITED SOURCE OF RETURN AIR | | | PER FBCR M1602.2. THE HVAC RETURN CAN NOT SERVE AS A | | | SOURCE OF MAKE UP AIR FOR THE GAS DRYER PER FBCR | | | M1701.1. SUBMIT A REVISED PLAN SHOWING AN APPROVED | | | SOURCE OF COMBUSTION AIR FOR THE GAS DRYER AS SPECIFIED | | | IN FBCR M1701.1. NOTE: A LOUVER DOOR ON THE LAUNDRY | | | ROOM WOULD BE ACCEPTABLE. |
|