| Plan Review Notes For Permit 11120399 |
| Permit Number |
11120399 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2012-05-22 10:48:15 | BUILDING PROVISO | | | REVISION REQUIRED | | | | | | 1) SUBMIT REVISED PLANS SHOWING THAT THE ATTACHED | | | GARAGE HAS A FINISHED FLOOR ELEVATION OF 7.5 FEET OR IS | | | DESIGNED IN COMPLIANCE WITH NFIP REGULATIONS AND FEMA | | | REQUIREMENTS FOR ENCLOSED GARAGES AND NON-HABITABLE | | | SPACES WITH FLOORS BELOW BFE. NOTE: NO EQUIPMENT OR | | | MATERIALS THAT ARE NOT FLOOD DAMAGE-RESISTANT ARE | | | ALLOWED BELOW THE BFE. | | | WWW.FEMA.GOV/LIBRARY/FILE?TYPE=PUBLISHEDFILE&FILE=FEMA. | | | | | | NOTE: THE TRUSS DRAWINGS AND LAYOUT THAT WAS SUBMITTED | | | IS FOR THE 2010 FBC AND ASCE7-10. PROVIDE TRUSS DRAWING | | | AND LAYOUT DESIGNED TO THE 2007 FBC AND ASCE 7-05 TO | | | CORRESPOND WITH THE BUILDINGS DESIGN TO THE STRUCTURAL | | | INSPECTOR IN THE FIELD. |
|