| 2012-01-31 09:13:31 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY PLUMBING | | | | | | 1) FBCR P 3108.2 STATES THAT IN A HORIZONTAL WET- VENT | | | SYSTEM, NOT MORE THAN ONE WET-VENTED FIXTURE DRAIN | | | SHALL DISCHARGE UPSTREAM OF THE DRY-VENTED FIXTURE | | | DRAIN. TWO SECOND FLOOR BATHROOMS AND THE FIRST FLOOR | | | BATH AND LAUNDRY DO NOT COMPLY. | | | | | | 2) SHEET A-1 SHOWS A WET BAR ON THE FIRST FLOOR THAT IS | | | NOT INDICATED ON THE PLUMBING RISER PLAN ON SHEET S-1. | | | PLEASE CORRECT. CITY AMENDMENTS 106.1.1 | | | | | | 3) THE PLUMBING RISER PLANS SHOWS AN EXTRA LAVATORY AND | | | WATER CLOSET THAT IS NOT SHOWN ON THE ARCHITECTURAL | | | DRAWINGS. PLEASE CORRECT. CITY AMENDMENTS 106.1.1 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|