| Plan Review Notes For Permit 11120399 |
| Permit Number |
11120399 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-01-31 11:43:40 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY MECHANICAL | | | | | | 1) THE ENERGY CALCULATION FORM IS REQUIRED TO BE SIGNED | | | BY THE OWNER/AGENT. | | | | | | 2) PROVIDE AN EQUIPMENT SCHEDULE ON THE MECHANICAL | | | PLANS THAT CORRESPONDS WITH THE EQUIPMENT SIZING | | | CALCULATIONS. SPECIFY THE SERIAL NUMBERS OF THE | | | EQUIPMENT THAT WILL BE USED. | | | | | | 3) FBCR M1602.4 REQUIRES TRANSFER DUCTS TO TO BE ONE | | | AND ONE HALF TIMES THE CROSS SECTIONAL AREA OF THE | | | SUPPLY DUCT ENTERING THE ROOM OR SPACE IT'S SERVING AND | | | THE DOOR HAVING AT LEAST AN UNRESTRICTED 1 INCH | | | UNDERCUT TO ACHIEVE PROPER RETURN AIR BALANCE. | | | | | | 4) SHOW COMPLIANCE WITH FBCR G2407 (304) AND G2439.4 | | | (614.5) AS TO HOW MAKEUP AIR FOR THE GAS DRYER WILL BE | | | PROVIDED. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|