2012-01-31 11:43:402007 FBC W/2009 REVISIONS
  
 DENIED BY MECHANICAL
  
 1) THE ENERGY CALCULATION FORM IS REQUIRED TO BE SIGNED
 BY THE OWNER/AGENT.
  
 2) PROVIDE AN EQUIPMENT SCHEDULE ON THE MECHANICAL
 PLANS THAT CORRESPONDS WITH THE EQUIPMENT SIZING
 CALCULATIONS. SPECIFY THE SERIAL NUMBERS OF THE
 EQUIPMENT THAT WILL BE USED.
  
 3) FBCR M1602.4 REQUIRES TRANSFER DUCTS TO TO BE ONE
 AND ONE HALF TIMES THE CROSS SECTIONAL AREA OF THE
 SUPPLY DUCT ENTERING THE ROOM OR SPACE IT'S SERVING AND
 THE DOOR HAVING AT LEAST AN UNRESTRICTED 1 INCH
 UNDERCUT TO ACHIEVE PROPER RETURN AIR BALANCE.
  
 4) SHOW COMPLIANCE WITH FBCR G2407 (304) AND G2439.4
 (614.5) AS TO HOW MAKEUP AIR FOR THE GAS DRYER WILL BE
 PROVIDED.
  