2012-01-18 17:47:5211120399
 103 ARLINGTON PL
 CONSTRUCT A NEW SFD
  
 ADD RECEPTACLES SO THAT NO WALL SPACE IS MORE THAN 6
 FEET FROM A RECEPTACLE AND ALL WALL SPACES MORE THAN 2
 FEET IN WIDTH HAVE A RECEPTACLE. NEC 210.52
 ALL GENERAL PURPOSE BRANCH CIRCUITS MUST BE PROTECTED
 WITH ARC FAULT CIRCUIT INTERRUPTERS. NEC 210.12
 CARBON MONOXIDE ALARMS ARE REQUIRED WITHIN 10 FEET OF
 ALL SLEEPING AREAS. FBC R313
 MINIMUM SIZE ELECTRIC SERVICE CONDUCTORS ARE 3/0 COPPER
 OR 250 MCM ALUMINUM. NEC T. 310.15 (B) (6)
 AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN
 SERVICE GROUND NEC 250.94
 BATHROOMS EACH REQUIRE A DEDICATED 20 AMP BRANCH
 CIRCUIT. NEC 210.11 (C) (3)
 TAMPER RESISTANCE RECEPTACLES ARE REQUIRED. NEC 406.11