| 2012-01-18 17:47:52 | 11120399 | | | 103 ARLINGTON PL | | | CONSTRUCT A NEW SFD | | | | | | ADD RECEPTACLES SO THAT NO WALL SPACE IS MORE THAN 6 | | | FEET FROM A RECEPTACLE AND ALL WALL SPACES MORE THAN 2 | | | FEET IN WIDTH HAVE A RECEPTACLE. NEC 210.52 | | | ALL GENERAL PURPOSE BRANCH CIRCUITS MUST BE PROTECTED | | | WITH ARC FAULT CIRCUIT INTERRUPTERS. NEC 210.12 | | | CARBON MONOXIDE ALARMS ARE REQUIRED WITHIN 10 FEET OF | | | ALL SLEEPING AREAS. FBC R313 | | | MINIMUM SIZE ELECTRIC SERVICE CONDUCTORS ARE 3/0 COPPER | | | OR 250 MCM ALUMINUM. NEC T. 310.15 (B) (6) | | | AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN | | | SERVICE GROUND NEC 250.94 | | | BATHROOMS EACH REQUIRE A DEDICATED 20 AMP BRANCH | | | CIRCUIT. NEC 210.11 (C) (3) | | | TAMPER RESISTANCE RECEPTACLES ARE REQUIRED. NEC 406.11 | | | NEC | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | |
|