Plan Review Notes
Plan Review Notes For Permit 11120399
Permit Number 11120399
Review Stop B
Sequence Number 1
Notes
Date Text
2012-01-31 14:57:232007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) SPECIFY THE PROPOSED FINISHED FLOOR ELEVATIONS ON
 THE PLANS. THE MINIMUM F.F. ELEVATION FOR THIS PROJECT
 IS 7.5' BFE. SEE CITY AMENDMENTS 106.1.1 AND WPB
 MUNICIPAL CODE.
  
 2) ON SHEET A-7 R-19 SPRAY FOAM INSULATION AND A
 NON-VENTED ATTIC IS SPECIFIED AND ON THE ENERGY
 CALCULATION FORM SPECIFIES A VENTED ATTIC WITH R-30
 INSULATION. PLEASE CLARIFY. CITY AMENDMENTS 106.1.1
  
 3) SUBMIT TWO COPIES OF THE EVALUATION REPORTS FOR THE
 SPRAY FOAM INSULATION THAT WILL BE INSTALLED. FBC R314
  
 4)THE COMPONENT AND CLADDING PRESSURES SPECIFIED FOR
 THE DOORS AND WINDOWS ARE TOO LOW FOR 140 MPH, EXPOSURE
 CATEGORY C WITH A MEAN ROOF HEIGHT OF 30 FEET. FOR
 EXAMPLE THE 20 SQFT WINDOWS IN WALL ZONE 5 ARE LISTED
 AS +45.2, -58.9 PSF AND THEY SHOULD BY +47.2,-61.7 PSF.
 PLEASE REVIEW THE PRESSURES. FBC R301.2.1
  
 5) THE STRUCTURE IS LOCATED WITHIN 600 FEET OF THE
 INTER-COASTAL WATERWAY, THEREFORE, FBC R301.2.1.4.3
 REQUIRES THE ROOF TO WALL AND ROOF SHEATHING UPLIFT
 LOADS TO BE INCREASED BY 20 PERCENT. SHOW COMPLIANCE.
  
 6) THE ENERGY CALCULATION FORMS SPECIFY R-5 WALL
 INSULATION AND SHEET A-7 OF THE PLANS HAS R3.3. PLEASE
 CORRECT.
  
 7) THE ROOF ZONE DIAGRAM ON SHEET A-8 IS INCORRECT. THE
 CORNERS OF THE ROOFS ARE ZONE 3, INCLUDING HIP ROOFS.
 PLEASE CORRECT. SEE FBCR FIGURE R301.2(7).
  
 8) SPECIFY THE WATERPROOFING ASSEMBLY THAT WILL BE
 INSTALLED ON THE BALCONIES. TWO LAYERS OF 30# FELT
 BETWEEN THE CDX SHEATHING AND CEMENT BOARD IS NOT
 ACCEPTABLE. FBC R903
  
 9) SPECIFY THE TYPE OF WELDS THAT WILL BE USED TO
 ATTACH THE BASE AND CAPS TO THE TUBE STEEL COLUMNS.
 CITY AMENDMENTS 106.1.1
  
 10) SHOW COMPLIANCE WITH FBC R311.4.3 FOR MINIMUM
 DIMENSION REQUIREMENTS OF LANDINGS THAT ARE REQUIRED AT
 EXTERIOR DOORS.
  
 11) PROVIDE A TRUSS ANCHOR SCHEDULE. SPECIFY TRUSS
 ANCHORS AND UPLIFT PRESSURES. FBCR802.1.6.5
  
 12) SHOW COMPLIANCE WITH FBC R 309.2 FOR GARAGE
 SEPARATION FROM HABITABLE ROOMS LOCATED ABOVE.
  
 13) SHOW COMPLIANCE WITH FBC R 313.4 FOR CARBON
 MONOXIDE ALARMS.
  
 14) THE COMPONENT & CLADDING PRESSURES FOR THE OVERHEAD
 GARAGE DOOR AND THE DOOR FROM THE MASTER BEDROOM TO THE
 BALCONY ARE NOT SPECIFIED ON THE PLANS. PLEASE PROVIDE.
 FBC R301.2.1
  
 15) THE FOLLOWING PRODUCT APPROVALS HAVE BEEN
 SUPERSEDED: NOA NO.10-0819.05 MULLIONS, NOA NO.
 07-0629.10 FRENCH DOORS AND NOA NO. 08-0820.14 SINGLE
 HUNG WINDOWS. SUBMIT CURRENT PRODUCT APPROVALS. DCA
 RULE 9N-3. NOAS CAN BE FOUND AT THE FOLLOWING WEBSITE:
 HTTP://WWW.MIAMIDADE.GOV/BUILDING/PC-SEARCH_APP.ASP
  
 16) THE PRODUCT APPROVAL FOR THE DOUBLE OUTSWING STEEL
 DOORS, NOA NO.07-0509.07, ARE LIMITED TO A MAXIMUM
 HEIGHT OF 6' 8" FOR DOUBLE DOORS AND 7'0" FOR SINGLE
 DOORS. THE PLANS SPECIFY 8'0" DOORS. PLEASE CORRECT.
  
 17) THE PRODUCT APPROVAL FOR THE FIXED GLASS WINDOWS,
 NOA NO. 08-0820.15, HAS A MAXIMUM SIZE LIMIT OF 63" X
 31.5" FOR THE ARCHED WINDOWS AND 48" X 62" FOR THE
 RECTANGULAR WINDOWS. THE ONES ON THE PLANS ARE LARGER.
 PLEASE CORRECT.
  
 18) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE 48"
 ROUND FIXED GLASS WINDOW, AS REQUIRED BY DCA RULE 9N-3.
  
 19) PLEASE SUBMIT A RESPONSE LETTER THAT INDICATES HOW
 EACH OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]