| Plan Review Notes For Permit 11120396 |
| Permit Number |
11120396 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-01-09 14:12:31 | PLANS DENIED | | | 1) PROVIDE FRESH AIR CALCULATIONS ON THE PLANS.PER | | | SECTION 403.3 2007 FBC (M). | | | 2) SHOW FRESH AIR DUCT ON THE PLANS. | | | 3) REFER TO SECTION 13-409.AB.3.3 SHUTOFF DAMPER | | | CONTROL. 2007 ENERGY CODE. | | | 4) PROVIDE BATHROOM EXHAUST ON THE PLANS. PER SECTION | | | 402.3.1 FBC (M) 2007. | | | 5) PROVIDE EQUIPMENT SCHEDULE SHOWING SEER, VOLTAGE. | | | 6) PROVIDE COOLING LOAD CALCULATIONS WITH THE PLANS | | | .PER SECTION 13-407.AB.1 | | | 2007 ENERGY CODE. | | | 7) SHOW VOLUME DAMPERS ON THE PLANS. PER SECTION 603.17 | | | FBC(M) 2007 | | | PLAN REVIEW BY HAROLD MOSER | | | 561-805-6732 | | | [email protected] |
|