Plan Review Notes
Plan Review Notes For Permit 11120396
Permit Number 11120396
Review Stop M
Sequence Number 1
Notes
Date Text
2012-01-09 14:12:31PLANS DENIED
 1) PROVIDE FRESH AIR CALCULATIONS ON THE PLANS.PER
 SECTION 403.3 2007 FBC (M).
 2) SHOW FRESH AIR DUCT ON THE PLANS.
 3) REFER TO SECTION 13-409.AB.3.3 SHUTOFF DAMPER
 CONTROL. 2007 ENERGY CODE.
 4) PROVIDE BATHROOM EXHAUST ON THE PLANS. PER SECTION
 402.3.1 FBC (M) 2007.
 5) PROVIDE EQUIPMENT SCHEDULE SHOWING SEER, VOLTAGE.
 6) PROVIDE COOLING LOAD CALCULATIONS WITH THE PLANS
 .PER SECTION 13-407.AB.1
 2007 ENERGY CODE.
 7) SHOW VOLUME DAMPERS ON THE PLANS. PER SECTION 603.17
 FBC(M) 2007
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]