2011-12-16 12:03:361810 SOUTH DIXIE HIGHWAY
 PERMIT #11120396
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE BUILDING IS FUNCTIONING AS A MULTIUSE OCCUPANCY.
 INDICATE IF THE BUILDING IS DESIGNED FOR MIXED USE
 (NON-SEPARATED) OR SEPARATED USE. FOR SEPARATED USE,
 THE BUSINESS OCCUPANCY REQUIRES A TWO-HOUR FIRE
 SEPARATION FROM THE MERCANTILE OCCUPANCY PER TABLE
 6.1.14.4.1B OF NFPA 101 FLORIDA EDITION 2006.
  
 NOTE: A ONE-HOUR TENANT SEPARATION IS REQUIRED.
  
 EACH NEW SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE
 PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING
 FIRE/SMOKE BARRIER-PROTECT ALL OPENINGS. CHARACTERS
 SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN
 WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15
 FEET ON CENTER. REFERENCE SECTION 8.3.2.4 OF FLORIDA
 FIRE PREVENTION CODE - NFPA 101
  
 OPENINGS AND PENETRATIONS THROUGH A FIRE-RATED WALL
 ASSEMBLY SHALL BE PROTECTED BY A FIRESTOP SYSTEM OR
 DEVICE. REFERENCE SECTION 8.3.5.1 OF FLORIDA FIRE
 PREVENTION CODE - NFPA 101
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  