| Plan Review Notes For Permit 11120396 |
| Permit Number |
11120396 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-01-04 14:54:06 | 11120396 | | | | | | SHOW LOCATION OF ALL ELECTRICAL SERVICE EQUIPMENT ON | | | THE PLAN. UNUSED ELECTRIC FIXTURES ETC. SHALL BE | | | REMOVED. SOME RECEPTACLES ARE NOT SHOWN ON PLAN. IS | | | THIS A NEW SERVICE OR EXISTING? DOES THE ELECTRIC | | | SERVICE SHOWN PROVIDE POWER TO THE WHOLE BUILDING? NEC | | | 215.5 | | | ALL ELECTRICAL SERVICE DISCONNECTS SHALL BE GROUPED IN | | | ONE LOCATION. NEC 230 72 | | | GFCI PROTECTION IS REQUIRED FOR THE ELECTRIC WATER | | | COOLER. | | | GFCI PROTECTION IS REQUIRED FOR RECEPTACLES SERVING THE | | | KITCHENETTE (NOT SHOWN). NEC 210.8 | | | PROVIDE AN INTERSYSTEM BONDING STRIP AT THE SERVICE. | | | NEC 250.94 | | | | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|