| Plan Review Notes For Permit 11120372 |
| Permit Number |
11120372 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2012-05-08 09:12:10 | NEW PLANS DO NOT MATCH PREVIOUSLY REVIEWED PLANS. | | | PLEASE PROVIDE THE FOLLOWING. | | | | | | 11120372 | | | 437 8TH ST. | | | REMODEL | | | | | | ALL NEW BRANCH CIRCUITS MUST BE PROTECTED WITH ARC | | | FAULT CIRCUIT INTERRUPTERS. 2008 NEC 210.12 | | | SHOW SERVICE RISER PLAN AND LOCATION OF SERVICE. NEC | | | 215.15 | | | ADD RECEPTACLES IN THE KITCHEN, FOR THE COUNTER TOP AND | | | THE ADJOINING ROOM OF THE SECOND FLOOR UNIT. NEC 210.52 | | | PROVIDE AN INTERSYSTEM BONDING STRIP AT THE ELECTRICAL | | | SERVICE. NEC 250.94 | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|