| Plan Review Notes For Permit 11120371 |
| Permit Number |
11120371 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2012-02-29 08:34:03 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY BUILDING | | | | | | 1) THE WINDOW AND DOOR PRESSURES SPECIFIED ON THE PLANS | | | OF +49.3 & - 66.0 PSF ARE HIGHER THAN THE PRODUCT | | | APPROVAL DESIGN PRESSURES FOR THE WINDOWS (+ / - 55.7 | | | PSF) AND DOORS ( + / - 50 PSF). SUBMIT TWO COPIES OF | | | PRODUCT APPROVALS FOR WINDOWS AND DOORS WITH ADEQUATE | | | DESIGN PRESSURES. FBC R301.2.1 AND DCA RULE 9N-3. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|