| Plan Review Notes For Permit 11120371 |
| Permit Number |
11120371 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-01-10 17:41:49 | 11120371 | | | 437 8TH STREET | | | RESIDENTIAL ADDITION | | | | | | SHOW LOCATION OF THE NEW SERVICE. NEC 215.15 | | | THE REQUIRED INTERSYSTEM BONDING STRIP NEEDS TO BEEN | | | SHOWN ON THE SERVICE RISER PLAN. NEC 250.94 | | | ALL NEW BRANCH CIRCUITS MUST BE PROTECTED WITH ARC | | | FAULT CIRCUIT INTERRUPTERS. 2008 NEC 210.12 | | | MAIN ELECTRICAL DISCONNECTS MUST BE SERVICE RATED AND | | | GROUPED IN ONE LOCATION. THE DRAWING IS UNCLEAR AS TO | | | HOW THE TWO METERS AND RISERS FUNCTION. A BUILDING | | | SHOULD ONLY HAVE ONE POINT OF SERVICE. NEC 230.2, | | | 230.40 | | | AT LEAST ONE GFCI PROTECTED RECEPTACLE IS REQUIRED | | | OUTSIDE FRONT AND BACK. NEC 210.70 | | | ADD RECEPTACLES SO THAT NO WALL SPACE IS MORE THAN 6 | | | FEET FROM A RECEPTACLE AND ALL WALL SPACES MORE THAN 2 | | | FEET IN WIDTH HAVE A RECEPTACLE. NEC 210.52 | | | SMOKE ALARMS ARE REQUIRED TO BE INTERCONNECTED AND | | | LOCATED BOTH INSIDE AND OUT SIDE EACH SLEEPING AREA. | | | FBC R313.3 | | | EACH BATHROOM REQUIRES A DEDICATED 20 AMPERE BRANCH | | | CIRCUIT. NEC 210.11 | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|