| 2012-01-10 10:44:51 | 2007 FBC W/2009 REVISIONS |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) THE SURVEYS THAT WERE SUBMITTED ARE NOT FOR THIS |
| | PROPERTY. SUBMIT THE CORRECT SURVEYS. CITY AMENDMENTS |
| | 106.1 |
| | |
| | 2) SHEET E-1 OF THE PLANS SPECIFIES THAT THIS IS AN |
| | EXISTING DUPLEX. THE ZONING COMMENTS AND TENANT |
| | SEPARATION WALL DETAIL ON PLAN SHEET 1 INDICATE THAT |
| | THIS IS A SINGLE FAMILY RESIDENCE THAT IS BEING |
| | CONVERTED TO A DUPLEX. IF THIS IS AN EXISTING DUPLEX, |
| | PLEASE PROVIDE DOCUMENTATION THAT IT WAS BUILT WITH THE |
| | REQUIRED PERMITS. CITY AMENDMENTS 105 |
| | |
| | 3) SHOW COMPLIANCE WITH FBC R 317.1 WHICH REQUIRES THE |
| | ONE HOUR FIRE RATED DWELLING SEPARATION WALL TO EXTEND |
| | TO THE UNDERSIDE OF THE ROOF SHEATHING. EXCEPTION (2) |
| | ALLOWS THE SEPARATION WALL TO STOP AT THE CEILING, IF |
| | IT IS PROTECTED WITH 5/8" TYPE X GYPSUM BOARD AND THERE |
| | IS AN ATTIC DRAFTSTOP CONSTRUCTED AS SPECIFIED IN |
| | R502.12.1 ABOVE AND ALONG THE WALL ASSEMBLY SEPARATING |
| | THE DWELLINGS. |
| | |
| | 4) AT THE ONE FIRE RATED SEPARATION WALL THE 5/8" TYPE |
| | X DRYWALL IS REQUIRED TO EXTEND PAST THE TUB DOWN TO |
| | THE FLOOR AND ALL PENETRATIONS ARE REQUIRED TO BE |
| | PROTECTED PER FBCR 317.3. |
| | |
| | 5) SHOW THE LOCATIONS AND SIZES OF THE ATTIC ACCESSES |
| | IN EACH UNIT. FBC R807.1 |
| | |
| | 6) THE SUBMITTED PLANS INCLUDE AN ISOMETRIC PLUMBING |
| | RISER PLAN AND ELECTRIC PLANS WHICH INDICATE THAT A |
| | SINGLE FAMILY DWELLING IS BEING CONVERTED TO A TWO |
| | FAMILY DWELLING OR HAS BEEN ILLEGALLY CONVERTED. PLEASE |
| | PROVIDE AN EXISTING FLOOR PLAN AND A PROPOSED FLOOR |
| | PLAN TO CLARIFY THE SCOPE OF WORK. CITY AMENDMENTS |
| | 106.1.1 |
| | |
| | 7) IF A SINGLE FAMILY DWELLING IS BEING CONVERTED TO A |
| | TWO FAMILY DWELLING, THEN THE PLANS ARE REQUIRED TO BE |
| | REVIEWED BY PALM BEACH COUNTY FOR IMPACT FEES. |
| | |
| | 8) ON PLAN SHEET 2, THE WINDOW AND DOOR PRESSURES ARE |
| | SPECIFIED AS +35.3 PSF AND -47.2 PSF AND THE EXPOSURE |
| | CATEGORY THAT IS SPECIFIED IS C. THESE PRESSURES ARE |
| | WORSE CASE FOR EXPOSURE CATEGORY B. PLEASE CORRECT. FBC |
| | R301.2.1 |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |