| 2012-03-14 10:32:49 | BUILDING PLAN REVIEW |
| | PERMIT: 11120195 |
| | ADD: 8264 NORTHLAKE BLVD |
| | CONT: TO BE DETERMINED |
| | TEL: (561)805-6700 SAM DORFMAN |
| | |
| | 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | ACTION: DENIED |
| | |
| | A REPRESENTATIVE NEEDS TO COME IN AND COLLATE THE PLANS |
| | INTO TWO SETS WITH THE NEW SHEETS INSERTED AND THE OLD |
| | SHHEETS PULLED OUT BEFORE THE REVIEW CAN TAKE PLACE. |
| | |
| | |
| | |
| | |
| | 1A) SHEET D1.0 NOTES D1-3 INDICATE THE REUSE OF |
| | ANDERSON WOOD WINDOWS AND DOORS. THIS BUILDING (PERMIT |
| | # 94013940) WAS BUILT UNDER THE 1991 SBCCI AND THE WIND |
| | SPEED WAS 110 MPH FASTEST MILE THAT CONVERTS OVER TO |
| | 130 MPH 3 SECOND GUST UNDERTHE 2007/ 09 FBC-B. HOW WILL |
| | YOU DEMONSTRATE CODE COMPLIANCE FOR WIND FOR THE |
| | ANDERSON WINDOWS AND DOORS? 2007/09 FBC-B 1609 |
| | COMPONENTS & CLADDING FOR WIND PRESSURES? |
| | |
| | 1B) THERE WERE NO PRODUCT APPROVAALS SUBMITTED FOR THE |
| | ANDERSON WINDOWS AND DOOR NOR WERE THERE ANY PLANS |
| | INDICATING THE TYPE OF FASTENERS TO BE USED IN |
| | ANCHORING THE WINDOWS AND DOORS NOR THE SPACING OF |
| | ANCHORS. |
| | |
| | 1C) THE PLANS ALSO INDICATE THERE TO BE STORM SHUTTERS |
| | TO BE USED FOR COMPLIANCE WITH THE REQUIREMENT FOR |
| | LARGE MISSILE IMPACT COMPLIANCE, PLEASE PROVIDE |
| | DOCUMENTATION THAT THE STORM SHUTTERS WILL MEET THE |
| | REQUIREMENT FOR LARGE MISSILE AND WIND, 2007/09 FBC-B |
| | 1609 COMPONENTS AND CLADDING. |
| | |
| | 2) THE PLANS DO NOT PROVIDE ANY FASTENING OF FRAMING, |
| | SIDING, DECKING, OR ROOF SHEATHING, THE FASTENING |
| | TABLES FOUND IN FBC TABLE 2304.9.1 ARE FOR WIND ZONES |
| | WITH LESS THAN 100 MPH WINDS. 2007/09 FBC-B 2308.2 (4). |
| | |
| | 3) SHEET A2.3 INDICATES THE ROOFING PRODUCT APPROVAL # |
| | 08-0226.06 POLYGLASS SYSTEM, ONCE THE CONTRACTOR IS |
| | AWARDED THE CONTRACT, THE CONTRACTOR WILL NEED TO |
| | IDENTIFY WHICH SUB-SYSTEM TO BE INSTALLED, PLEASE NOTE |
| | SOME OF THE SUB-SYSTEMS MAY REQUIRE INHANCED FASTENING |
| | IN ZONES 2 & 3. |
| | |