| Plan Review Notes For Permit 11120157 |
| Permit Number |
11120157 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-12-09 16:25:20 | NOTE: THIS ALTERATION DOES NOT MEET THE 50% RULE FOUND | | | IN THE 2007/09 FL. EXISTING BUILDING CODE SECTION | | | 703.2.2 SUPPLEMENTAL SHAFT | | | AND FLOOR OPENING ENCLOSURE REQUIREMENTS, (ELEVATOR | | | LOBBIES). WHEN LESS THAN 50% OF THE FLOOR PLATE IS | | | BEING REMODELED THEN THE | | | ELEVATOR LOBBY AND EXCEPTIONS WILL NOT BE ENFORCED. | | | 2007/09 FL B C- 707.14 ELEVATOR LOBBIES | | | | | | BUILDING PROVISO: | | | THE FILE ROOM # 1609 IS LARGER THAN 100'-0" SQ FT. | | | PLEASE REVIEW FBC-B 508.2.2.1 CONSTRUCTION FOR WALLS, | | | FOR INCIDENTAL USE AREAS. | | | THE INCIDENTAL USE AREA SHALL BE SEPARATED FROM THE | | | REMAINDER OF THE BUILDING BY CONSTRUCTION CAPABLE OF | | | RESISTING THE PASSAGE OF SMOKE. | | | THE PARTITIONS SHALL EXTEND FROM THE FLOOR TO THE | | | UNDERSIDE OF THE FIRE-RESISTANCE-RATED FLOOR/CEILING | | | ASSEMBLY OR FIRE-RESISTANCE-RATED ROOF/ | | | CEILING ASSEMBLY ABOVE OR TO THE UNDERSIDE OF THE FLOOR | | | OR ROOF SHEATHING, OR SUB DECK ABOVE. DOORS SHALL BE | | | SELF- OR AUTOMATIC CLOSING | | | UPON DETECTION OF SMOKE IN ACCORDANCE WITH SECTION | | | 715.4.7.3. DOORS SHALL NOT HAVE AIR TRANSFER OPENINGS | | | AND SHALL NOT BE UNDERCUT | | | IN EXCESS OF THE CLEARANCE PERMITTED IN ACCORDANCE WITH | | | NFPA 80. |
|