| Plan Review Notes For Permit 11120116 |
| Permit Number |
11120116 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-01-09 10:15:55 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY BUILDING | | | | | | 1) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE 3" | | | INSULATED ROOF PANELS THAT WILL BE INSTALLED AS | | | REQUIRED BY DCA RULE 9N-3. | | | | | | 2) SPECIFY THE HEIGHT OF THE MANSARD ON THE PLANS. CITY | | | AMENDMENTS 106.1.1 | | | | | | 3) THE 2 X 7 COLUMNS WITH 8'-0" SPACING ARE LIMITED TO | | | A HEIGHT OF 8'-3" BASED ON THE TABLES AND THE STRUCTURE | | | REQUIRES 12'-0" COLUMNS. PLEASE REVISE. FBC R301.1 | | | | | | 4) SHOW THAT THE DOUBLE 2 X 10 CARRIER BEAM IS CAPABLE | | | OF SPANNING 17'-6" AND SAFELY SUPPORTING ALL LOADS, | | | INCLUDING THE TRIBUTARY LOADS OF THE INSULATED PANEL | | | ROOF AND THE SCREEN ROOM ROOF. FBC R301.1 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|