| Plan Review Notes For Permit 11120079 |
| Permit Number |
11120079 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-01-05 15:08:14 | 11120079 | | | 219 AVILA RD. | | | RESIDENTIAL ADDITION | | | | | | ELECTRICAL RISER PLAN IS NOT CLEARLY LEGIBLE. PLEASE | | | RESUBMIT. NEC 215.5 | | | PANEL BOARD FEEDERS ARE UNDERSIZED. MINIMUM #3/0, AND | | | #3 REQUIRED. NEC 310.16 | | | PLEASE LOCATE THE CARBON MONOXIDE ALARMS ON THE PLANS | | | IN ACCORDANCE WITH THE MANUFACTURER?S RECOMMENDATIONS. | | | PLAN NOTES ARE NOT AN ACCEPTABLE ALTERNATIVE. ADD A | | | CARBON MONOXIDE DETECTOR FOR THE 2ND FLOOR BEDROOMS | | | INCLUDING THE STUDIO. FBC R313 | | | IN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN | | | ELECTRIC SERVICE. NEC 250.94 | | | ADDITIONAL RECEPTACLES ARE REQUIRED IN THE FOYER. NEC | | | 210.52 | | | AC DISCONNECTS MAY NOT BE BLOCKED BY THE CONDITIONING | | | UNITS. NEC 110.26 | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | |
|