| 2011-12-22 16:49:02 | 2007 FBC W/2009 REVISIONS |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) ON SHEET A.02 AND A.03 THERE IS A SECTION MARK FOR |
| | SECTION 13 ON A.07. THERE IS NO SECTION 13 ON A.07. |
| | PLEASE CLARIFY. CITY AMENDMENTS 106.1.1 |
| | |
| | 2) ON SHEET A.02 THERE IS A SECTION THROUGH THE |
| | CONCRETE STAIRS AT THE GARAGE MARKED 13 ON A.07. THERE |
| | IS NO SECTION 13 ON A.07. PLEASE CLARIFY. CITY |
| | AMENDMENTS 106.1.1 |
| | |
| | 3) THE WINDER TREADS ON THE INTERIOR STAIRS ARE |
| | REQUIRED TO COMPLY WITH FBCR 311.5.3.2 WHICH REQUIRES A |
| | MINIMUM TREAD DEPTH OF 10" AT A POINT 12" FROM THE SIDE |
| | WHERE THE TREADS ARE NARROWER AND A MINIMUM TREAD DEPTH |
| | OF 6" AT ANY POINT. |
| | |
| | 4) PROVIDE A SECTION THROUGH THE GARAGE APARTMENT. |
| | SPECIFY THE INSULATION IN THE WALLS, CEILING AND FLOOR. |
| | CITY AMENDMENTS 106.1.1 |
| | |
| | 5) SHOW COMPLIANCE WITH FBC R309.2 FOR SEPARATION |
| | REQUIREMENTS BETWEEN GARAGE AND LIVING SPACE. |
| | |
| | 6) SUBMIT ROOF SCUPPER SIZING CALCULATIONS FOR THE |
| | GARAGE APARTMENT. SPECIFY THE LOCATIONS AND SIZES OF |
| | THE PRIMARY AND OVERFLOW SCUPPERS. FBC R903.4 |
| | |
| | 7) SHOW COMPLIANCE WITH FBC R320.7 WHICH REQUIRES |
| | GUTTERS WITH DOWNSPOUTS WITH OF LESS THAN 6 INCHES |
| | HORIZONTAL PROJECTION AND DOWNSPOUTS TO DISCHARGE AT |
| | LEAST ONE FOOT AWAY FROM THE STRUCTURE SIDE WALL. |
| | |
| | 8) THE COMPONENT AND CLADDING PRESSURES FOR THE WINDOW |
| | AND DOOR OPENINGS ON SHEETS A.02 AN A.03 OF THE |
| | ARCHITECTURAL PLANS DO NOT CORRESPOND WITH THE |
| | STRUCTURAL PLANS. THE PRESSURES ON THE ARCHITECTURAL |
| | PLANS ARE BASED ON EXPOSURE CATEGORY B AND THE |
| | STRUCTURAL PLANS ARE BASED ON EXPOSURE C. PLEASE |
| | CORRECT. FBC R301.2.1 |
| | |
| | 9) SOME OF THE PRODUCT APPROVALS SPECIFIED ON SHEET |
| | A.01 DO NOT CORRESPOND WITH THE PRODUCT APPROVALS THAT |
| | WERE SUBMITTED. PLEASE CORRECT. CITY AMENDMENTS 106.1.1 |
| | |
| | 10) THE DESIGN PRESSURES LISTED IN THE PRODUCT |
| | APPROVALS FOR SOME OF THE DOORS DO NOT MEET THE |
| | COMPONENT AND CLADDING PRESSURES FOR EXPOSURE C IN WALL |
| | ZONE 5. FBC R301.2.1 PLEASE REVIEW. |
| | |
| | 11) THE DOOR AT THE SIDE LOGGIA IS LABELED 2 ON A.02, |
| | WHICH IS THE OVER HEAD GARAGE DOOR. PLEASE CLARIFY. |
| | CITY AMENDMENTS 106.1.1 |
| | |
| | 12) SUBMIT TWO SETS OF EVALUATION REPORTS FOR THE SPRAY |
| | FOAM INSULATION TO SHOW COMPLIANCE WITH FBC R314. |
| | |
| | 13) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE DOUBLE |
| | FIXED LITE DOORS AS REQUIRED BY DCA RULE 9N-3. |
| | |
| | 14) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE |
| | CASEMENT WINDOWS AS REQUIRED BY DCA RULE 9N-3. THE ONES |
| | THAT WERE SUBMITTED ARE FOR PROJECTED WINDOWS (AWNING). |
| | |
| | 15) SPECIFY THE APPROVED ASSEMBLY AND FASTENING OPTION |
| | FROM THE PRODUCT APPROVAL THAT WILL BE USED TO INSTALL |
| | THE GAF MODIFIED ROOF SYSTEM. SUBMIT TWO SIGNED AND |
| | SEALED SETS OF RAS 117 CALCULATIONS FOR THE ENHANCED |
| | FASTENING OF THE BASE SHEET IN ORDER TO MEET THE HIGHER |
| | UPLIFT PRESSURES AT THE PERIMETER AND CORNER ROOF |
| | AREAS. FBC R905.12.3 |
| | |
| | 16) SPECIFY THE ATTACHMENT METHOD AND ATTACHMENT |
| | RESISTANCE MOMENT FROM THE CONCRETE ROOF TILE PRODUCT |
| | APPROVAL THAT WILL BE USED TO INSTALL THE TILE.FBC |
| | R905.3 |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |