| 2011-12-05 11:40:55 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS. | | | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | | | 1- PLEASE PROVIDE SIGNED AND SEALED RAS 117 | | | CALCULATIONS FOR NAIL ENHANCING AT PERIMETER AND CORNER | | | AREAS TO MEET THE DESIGN PRESSURES REQUIRED BY SEC. | | | R301.2.1.4.3. GENERAL LIMITATION #7 ON NOA 09-0224.01 | | | SUBMITTED REQUIRES CALCULATIONS TO BE SIGNED AND | | | SEALED. ***NOTE: DESIGN PROFESSIONAL DOING THE | | | CALCULATIONS TO TAKE INTO CONSIDERATION THAT THIS | | | BUILDING IS LOCATED ON EXPOSURE "C". SEE SEC. | | | R301.2.1.4.3. | | | | | | 2- PLEASE CLARIFY IF DOING AN INSULATED ROOF AND A | | | NON-INSULATED ROOF. PROVIDE RAS 117 CALCULATIONS FOR | | | EACH ONE. | | | | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|