| 2013-06-04 10:53:13 | PLANS DENIED | | | 1) PROVIDE PRODUCT APPROVALS FOR OUTSIDE LOVERS | | | PER SECTION 106.3.3 2007 FBC | | | 2) PROVIDE FRESH AIR CALCULATION ON THE PLANS | | | PER TABLE 403.3 FBC (M) | | | 3) PROVIDE A DETAIL BY THE ENGINEER SHOWING | | | CONDENSER STAND TO ROOF TIEDOWN.(BOLT OR SCREW SIZE) | | | 4) REFER TO SECTION 306.1 CLEARANCE FOR MAINTENANCE AND | | | REPLACEMENT | | | FOR VOLUME AND FIRE DAMPERS. | | | 5) PROVIDE MANUFACTURER'S INSTALLATION INSTRUCTIONS FOR | | | FIRE DAMPERS | | | 6) SEPARATE APPLICATION PLANS AND PERMIT REQUIRED FOR | | | HOOD, COOLERS & FREEZERS, GENERATOR AND FUEL TANK | | | 7) IN RESUBMITTING PLANS REMOVE AND REPLACE ANY PAGES | | | AS NECESSARY. | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|