| 2012-05-23 15:22:58 | FIRE STATION # 5 AND THE EMERGENCY OPERATIONS CENTER |
| | (EOC) |
| | 700 NORTH CONGRESS AVENUE |
| | NEW CONSTRUCTION |
| | PERMIT # 11120073 |
| | |
| | 1. ON COVER SHEET IT LISTS JONATHAN BRAMLEY AS |
| | ENGINEERING DIRECTOR. MR. BRAMLEY HAS LEFT THE CITY. |
| | |
| | 2. SEPARATE PLANS AND PERMITS REQUIRED FOR DIESEL FUEL |
| | AND LP GAS TANKS. |
| | |
| | 3. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE |
| | SPRINKLER SYSTEM. THE FIRE DEPARTMENT CONNECTION (FDC) |
| | IS TO BE LOCATED WITHIN 150 FEET OF A FIRE HYDRANT. |
| | |
| | 4. FIRE LINE BACKFLOW DEVICE IS TO BE EQUIPPED WITH |
| | TAMPER SWITCHES, CHAIN AND LOCK. |
| | |
| | 5. THE LARGE PAINTING OF THE STATION MASCOT (RHINO) IS |
| | TO BE SAVED FOR FUTURE USE DURING THE DEMOLITION PHASE |
| | OF THE PROJECT. THE PAINTING WILL BE INSTALLED IN THE |
| | NEW FIRE STATION. |
| | |
| | 6. THE SLIDING GATE WHEN INOPERATIVE, MUST BE ABLE TO |
| | BE OPENED MANUALLY. |
| | |
| | 7. EXIT SIGN IS MISSING ON SHEET LS-1 AT THE BOTTOM OF |
| | THE STAIR 3.51. |
| | |
| | 8. THE NOTE IN THE CODE ANALYSIS BOX IS INCORRECT. THE |
| | BUILDING IS EQUIPPPED WITH AN APPROVED FIRE SPRINKLER |
| | SYSTEM (NFPA 13) NOT (NFPA 75). |
| | |
| | 9. ON SHEET A-2.01 THERE APPEARS TO BE NUMEROUS CEILING |
| | MOUNTED SPEAKERS IDENTIFIED AS CS. IN MANYT CASES, THEY |
| | APPEAR TO BE DIRECTLY NEXT TO ONE ANOTHER. |
| | |
| | 10. THE NUMBER OF AVAILABLE SLEEPING ACCOMODATIONS WAS |
| | DISCUSSED WITH ALLAN ORTMAN ON MAY 22, 2012. HE |
| | EXPLAINED THAT DURING AN ACTUAL EVENT STAFFING WILL BE |
| | HELD AT A MINIMUM. |
| | |
| | 11. SMOKE DETECTORS WHEN INSTALLED SHALL BE A MINIMUM |
| | OF AT LEAST THREE FEET FROM AIR CONDITIONER DIFFUSERS. |
| | |
| | 12. ON SHEET A-3.01 THE ADDRESS IS ILLUSTRATED ON TWO |
| | ELEVATIONS. IT IS ONLY NEEDED ON ONE ELVATION. |
| | |
| | 13. FLOORING CORNERS SHOULD BE ROUNDED WHERE IT MEETS |
| | WALLS SO CORNERS CAN BE CLEANED. |
| | |
| | 14. PROVIDE SEPARATE PLANS AND PERMITS FOR ANY CLEAN |
| | AGENT SYSTEMS PLANNED TO BE INSTALLED. |
| | |
| | 15. MORE DETAILS NEEDED FOR SECURITY DEVICES PLANNED |
| | FOR DOORS. |
| | |
| | 16. THERE APPEARS TO BE NO EMERGENCY LIGHTING IN |
| | SEVERAL OFFICES ON THE FIRST AND SECOND FLOOR, WHEN |
| | NORMAL POWER IS LOST. WILL WORK BE ABLE TO BE PERFORMED |
| | IN THESE AREAS WHEN NORMAL POWER IS LOST. |
| | |
| | 17. EMERGENCY LIGHTS INSTALLED (GOGGLE EYES) ARE TO BE |
| | INSTALED AT AN ELEVATION THAT CAN BE TESTED. |
| | |
| | 18. NO FIRE ALARM DEVICES SHOWN IN VEHICLE BAY ON SHEET |
| | E-3.01. |
| | |
| | 19. ON PAGE E-3.03 THE FIRE ALARM CONTROL PANEL IS |
| | DISPLAYED. A MORE SUITABLE LOCATION IS TO BE PROVIDED |
| | ON THE FIRST FLOOR AND NOT LOCATED ON THE ROOF LEVEL. |
| | THE FIRE ALARM SYSTEM IS TO BE MONITORED BY A CENTRAL |
| | STATION APPROVED FOR CENTRAL STATION SERVICE. |
| | |
| | 20. PLEASE EXPLAIN PURPOSE OF THE CARD READERS SHOWN ON |
| | SHEET T-0.02. |
| | |
| | 21. ALL FIRE DAMPERS AFTER INSTALLATION ARE TO BE DROP |
| | TESTED TO ENSURE PROPER OPERATION. |
| | |
| | 22. SOFFITS OR ARCHITECTURAL DETAILS SHALL NOT |
| | INTERFERE WITH ANY OPERATION OF ANY FIRE SPRINKLER |
| | HEADS. |
| | |
| | |
| | DENIED |
| | |
| | |
| | MICHAEL E. CARSILLO, ASSISTANT FIRE CHIEF |
| | WEST PALM BEACH FIRE RESCUE |