| 2012-01-03 11:28:53 | THURSDAY, DECEMBER 29, 2011 | | | | | | 1120073 | | | 700 N. CONGRESS | | | NEW FIRE STATION | | | | | | VERIFY THE GENERATOR SERVICE DISCONNECT IS SERVICE | | | RATED AND IS GROUNDED FAULT PROTECTED (GFP) OR HAS A | | | GFP INDICATOR. SEE NEC 701.17 | | | THE ELECTRICAL PLAN IS UNCLEAR AS TO THE CLASSIFICATION | | | OF THE IT ROOMS UNDER THE ELECTRIC CODE. NEC 645.4 | | | THE ELECTRICAL PLAN IS UNCLEAR AS TO THE CLASSIFICATION | | | OF THE PREMISES WIRING UNDER THE ELECTRIC CODE FOR | | | CRITICAL OPERATIONS POWER SYSTEMS (COPS). NEC 708 | | | THE PLANS ARE UNCLEAR AS TO HOW THE IT ROOMS ARE TO BE | | | VENTILATED. NEC 645.4, 480.9 | | | PROVIDE A LABELING SCHEDULE FOR THE SAFETY SIGNAGE | | | REQUIRED FOR THE ELECTRICAL EQUIPMENT AND ELECTRICAL | | | ROOMS. NEC 110.22, 110.16, 701.9 | | | IDENTIFY THE MINIMUM WIRING METHOD PROPOSED IN ALL | | | CLASS 1 DIVISION 2 AREAS. NEC 501.10(B), 501.15(B) | | | ELECTRICAL CIRCUITS AND LIGHTING POLES HAVE NOT BEEN | | | SPECIFIED FOR THE SITE LIGHTING. | | | ELECTRICAL CIRCUITS SERVING LIVING AND SLEEPING AREAS | | | REQUIRE AFCI PROTECTION. NEC 210.12, 210.8 | | | | | | NOTE: SEPARATE PERMITS ARE REQUIRED FOR THE LIGHTNING | | | PROTECTION SYSTEM, SITE LIGHTING, AUDIO, SECURITY, DATA | | | AND PHONES. | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|