| 2011-12-28 15:20:55 | DENIED BY BUILDING |
| | |
| | 1) SPECIFY THE WIND DESIGN DATA ON THE PLANS. THE |
| | WIND-SPEED AND EXPOSURE CATEGORY ARE REQUIRED. FBC |
| | R301.2.1 |
| | |
| | 2) THE EXTERIOR STAIRS ARE REQUIRED BY FBC R301.1 TO |
| | PROVIDE A COMPLETE LOAD PATH THAT MEETS ALL |
| | REQUIREMENTS FOR THE TRANSFER OF ALL LOADS FOR THEIR |
| | POINT OF ORIGIN THROUGH THE LOAD RESISTING ELEMENTS TO |
| | THE FOUNDATION. SPECIFY ALL WOOD CONNECTORS, HANGERS, |
| | STRAPS, ETC. THAT WILL BE USED ON THE STAIRS TO MEET |
| | THIS REQUIREMENT. |
| | |
| | 3) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE NEW |
| | EXTERIOR DOORS AS REQUIRED BY DCA RULE 9N-3. |
| | |
| | 4) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE |
| | STRUCTURAL WINDOW MULLION AS REQUIRED BY DCA RULE 9N-3. |
| | |
| | 5) THE DRAWINGS SUBMITTED FOR THE IMPACT RATED SINGLE |
| | HUNG WINDOWS ARE INCOMPLETE. WHEN THEY WERE PRINTED THE |
| | DRAWINGS WERE NOT REDUCED TO FIT ON 8-1/2" X 11" PAPER. |
| | PLEASE SUBMIT COMPLETE DRAWINGS AS REQUIRED BY DCA RULE |
| | 9N-3. |
| | |
| | 6) FBC R613.6.1.1 BUCKS TO EXTEND BEYOND THE INTERIOR |
| | FACE OF THE WINDOW OR DOOR FRAME TO PROVIDE FULL |
| | SUPPORT OF THE FRAME. THE WINDOW BUCK DETAIL ON SHEET 2 |
| | SHOWS DRYWALL EXTENDING BEYOND THE INTERIOR FACE OF THE |
| | WINDOW FRAME. PLEASE REVISE. |
| | |
| | 7) THE VALUATION OF THE PREVIOUSLY COMPLETED WORK THAT |
| | IS SPECIFIED ON THE PERMIT APPLICATION OF $2500.00 IS |
| | TOO LOW. THE VALUATION FOR THE WORK INCLUDES ALL |
| | MATERIALS, LABOR, DESIGN FEES, OVERHEAD AND PROFIT |
| | REQUIRED TO COMPLETE THE SCOPE OF WORK. THE VALUATION |
| | FOR THE SCOPE OF WORK INCLUDES THE COSTS OF THE |
| | PREVIOUS WORK AS WELL ANY ADDITIONAL WORK REQUIRED TO |
| | ENSURE COMPLIANCE WITH THE BUILDING CODE. THE PLANS |
| | INDICATE THAT (18) EXTERIOR IMPACT WINDOWS AND (6) |
| | EXTERIOR DOORS WERE REPLACED, THE EXTERIOR STAIRS WERE |
| | REPLACED AND MODIFICATIONS TO THE FENCE AND STAIR ARE |
| | REQUIRED TO COMPLY WITH CODE. BASED ON MARSHALL AND |
| | SWIFT THE VALUATION FOR THE WINDOW AND DOOR REPLACEMENT |
| | ALONE IS $ 7,624.50. PLEASE ADJUST THE VALUATION. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | [email protected] |