| Notes |
| Date |
Text |
| 2011-12-02 14:03:01 | 777 SOUTH FLAGLER DRIVE - SUITE #1100 | | | PERMIT #11120021 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | PROVIDE VISUAL NOTIFICATION APPLIANCE IN CONFERENCE | | | #1106. VERIFY EXISTING NOTIFICATION APPLIANCES ARE | | | LOCATED IN LOUNGE, WAITING ROOM AND LARGE CONFERENCE | | | ROOM. | | | | | | DUE TO THE SIZE OF TRADING ROOM #1109 AN ADDITIONAL | | | HORN/STROBE WILL BE NEEDED FOR PROPER COVERAGE. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW | | | |
|