| Plan Review Notes For Permit 11110700 |
| Permit Number |
11110700 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2014-04-23 12:52:35 | BUILDING PLAN REVIEW | | | *******DENIED******* | | | ROBERT BROWN (561) 805 6652 | | | E-MAIL: [email protected] | | | | | | FLORIDA BUILDIING CODE 2010, SECTION 1604.2 - THE G.C. | | | LETTER, DATED 4/21/14, THAT WAS SUBMITTED TO CERTIFY | | | THE SHUTTER TRACK INSTALLATION IS NOT ACCEPTABLE UNLESS | | | THE SHUTTER TRACKS ARE FULLY SUPPORTED AS INTENDED BY | | | THE SHUTTER PRODUCT APPROVAL. THE REOMOVAL OF THE | | | BALCONY FLOOR TILE HAS LEFT A GAP UNDERNEATH THE | | | SHUTTER TRACKS. THE FASTENERS WILL BE SUBJECTED TO | | | CANTILEVER BENDING, AND THE SHUTTER TRACKS WILL BE | | | SUBJECTED TO TORSION, THAT WERE NOT CONTEMPLATED DURING | | | THE ENGINEERING AND TESTING PERFORMED IN SUPPORT OF THE | | | THE SHUTTER PRODUCT APPROVAL. PLEASE PROVIDE GROUT OR | | | ALTERNATIVE PACKING UNDER THE SHUTTER TRACKS, OR | | | PROVIDE ENGINEERING TO SHOW THAT REPEATED REVERSAL | | | (POSITIVE AND NEGATIVE) OF THE DESIGN WIND LOAD WILL | | | NOT CAUSE FAILURE OF THE SHUTTER TRACK OR THE | | | FASTENERS, OR SPALLING OF THE CONCRETE AROUND THE | | | FASTENERS. | | | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | | | END OF REVIEW COMMENTS | | | THE CODE REFERENCES GIVE ADDITIONAL INFO | | | TELEPHONE: (561) 805 6652 ROBERT BROWN | | | E-MAIL: [email protected] |
|