| Plan Review Notes For Permit 11110659 |
| Permit Number |
11110659 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-12-15 08:55:56 | FBC 2007 GAS REVIEW: | | | | | | PLEASE INCLUDE THE FOLLOWING ON THE GAS PLAN: | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL | | | CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER | | | FBC-2007 FUEL GAS. | | | | | | 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, | | | (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING | | | AND/OR SYSTEM PER THE FBC-2007 FUEL GAS APPENDIX A ? | | | USE OF CAPACITY SECTION A.3.1(4) | | | | | | PLEASE INCLUDE A DETAIL FOR THE 2 POUND TO 1/2 POUND | | | REGULATOR/S THAT WILL BE REQUIRED. | | | | | | REVIEW BY | | | LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | PHONE # 805-6692 | | | EMAIL [email protected] | | | FAX # 805-6676 | | | |
|