Plan Review Notes
Plan Review Notes For Permit 11110659
Permit Number 11110659
Review Stop G
Sequence Number 1
Notes
Date Text
2011-12-15 08:55:56FBC 2007 GAS REVIEW:
  
 PLEASE INCLUDE THE FOLLOWING ON THE GAS PLAN:
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC-2007 FUEL GAS.
  
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC-2007 FUEL GAS APPENDIX A ?
 USE OF CAPACITY SECTION A.3.1(4)
  
 PLEASE INCLUDE A DETAIL FOR THE 2 POUND TO 1/2 POUND
 REGULATOR/S THAT WILL BE REQUIRED.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  