 REVIEW COMMENTS - FIRE DEPARTMENT
  
 EACH NEW SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE
 PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING
 FIRE/SMOKE BARRIER-PROTECT ALL OPENINGS. CHARACTERS
 SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN
 WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15
 FEET ON CENTER.
  
 PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY SHALL
 BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE.
  
 NEW FIRE-RATED DOOR SHALL BE LABELED FOR 45 MINUTES AND
 BE SELF CLOSING.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  