| 2011-12-01 09:02:13 | 11110642 | | | 340 CLEMATIS ST. | | | INTERIOR RENOVATION | | | | | | PROVIDE AN ELECTRICAL PLAN WITH A PANEL SCHEDULE | | | SHOWING RATING, SIZE AND WIRING METHOD FOR THE NEW | | | ELECTRICAL CIRCUITS. NEC 210.3 | | | | | | ALL RECEPTACLES LOCATED WITH IN SIX FEET OF A SINK MUST | | | BE GFCI PROTECTED. NEC 210.8 | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | |
|