| Date |
Text |
| 2011-12-08 14:41:02 | 1700 SOUTH DIXIE HIGHWAY |
| | PERMIT #11110598 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS |
| | OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE |
| | REMOVED FROM THE SITE DAILY. |
| | |
| | PROVIDE BUILDING ADDRESS VISIBLE FROM THE STREET. |
| | NUMBERS SHALL BE ATTACHED TO THE BUILDING AND BE AT |
| | LEAST SIX-INCHES IN HEIGHT WITH 1-INCH STROKE AND SHALL |
| | CONTRAST THE BACKGROUND COLOR. ADDRESS TO FACE DIXIE |
| | HIGHWAY. |
| | |
| | PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY |
| | RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING |
| | NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM |
| | WWW.KNOXBOX.COM. |
| | |
| | THE BENCH TYPE SEATING COUNT NEEDS TO BE FIGURED INTO |
| | THE OCCUPANT LOAD CALCULATIONS. |
| | |
| | BOTH THE INDOOR AND OUTDOOR AREAS EXCEED AN OCCUPANT |
| | LOAD OF 50 PERSONS AND WILL REQUIRE TO TWO SEPARATE, |
| | DISTINCT EXITS. THE EXIT DISCHARGE OF THE OUTDOOR |
| | DINING EXIT LEADS BACK TO THE MAIN BUILDING ENTRANCE |
| | AND CANNOT BE CONSIDERED A SEPARATE EXIT. |
| | |
| | PROVIDE THE ARCHITECTURAL SEATING PLAN THAT IS BEING |
| | UTILIZED IN THE ENGINEERING DRAWINGS. |
| | |
| | PORTABLE FIRE EXTINGUISHERS SHALL HAVE A MINIMUM RATING |
| | OF 2A:10BC AND SHALL BE TAGGED BY A LICENSED FIRE |
| | EXTINGUISHER COMPANY. |
| | |
| | PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH |
| | EXIT SIGNS. |
| | |
| | FOR OCCUPANCIES WITH AN OCCUPANT LOAD OF 100 OR MORE |
| | PERSONS, PANIC HARDWARE SHALL BE PROVIDED ON DOORS TO |
| | RELEASE THE LOCK/LATCH. NO OTHER LOCKS OR LATCHES ARE |
| | PERMITTED THAT WOULD NOT BE RELEASED BY THE PANIC |
| | HARDWARE. AS A SUBSTITUTE FOR PANIC HARDWARE, THE MAIN |
| | ENTRANCE IS PERMITTED TO HAVE AN INTERIOR KEYED DOOR |
| | LOCK (AND NO LATCH) WITH A READILY VISIBLE SIGN STATING |
| | THIS DOOR TO REMAIN UNLOCKED WHEN THE BUILDING IS |
| | OCCUPIED. SIGN LETTERS SHALL BE AT LEAST 1 INCH IN |
| | HEIGHT. A THUMB TURN STYLE LOCK IS NOT PERMITTED TO BE |
| | SUBSTITUTED FOR A KEYED LOCK. |
| | |
| | EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS |
| | SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A |
| | CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM. |
| | SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF |
| | OCCUPANTS PERMITTED FOR EACH ROOM. |
| | |
| | EACH NEW SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE |
| | PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING |
| | FIRE/SMOKE BARRIER-PROTECT ALL OPENINGS. CHARACTERS |
| | SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN |
| | WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 |
| | FEET ON CENTER. |
| | |
| | PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY SHALL |
| | BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE. |
| | |
| | INDICATE THE HOURLY FIRE RATING OF THE FIRE DOORS. FIRE |
| | DOORS SHALL BE SELF CLOSING AND POSITIVE LATCHING. |
| | |
| | DEEP FAT FRYERS SHALL BE EQUIPPED WITH A SEPARATE |
| | HIGH-LIMIT CONTROL IN ADDITION TO THE ADJUSTABLE |
| | THERMOSTAT TO SHUT OFF FUEL OR ENERGY WHEN THE FAT |
| | TEMPERATURE REACHES 475F DEGREES AT 1 INCH BELOW THE |
| | SURFACE. |
| | |
| | SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE FIRE |
| | SPRINKLER SYSTEM, KITCHEN EXHAUST HOOD, AND HOOD |
| | SUPPRESSION SYSTEM. |
| | |
| | FIRE SPRINKLER SYSTEM SHALL BE MONITORED BY AN APPROVED |
| | SUPERVISING STATION IN ACCORDANCE WITH NFPA 72. |
| | |
| | WESLEY JOLIN |
| | WEST PALM BEACH FIRE RESCUE |
| | FIRE & LIFE SAFETY PLAN REVIEW |
| | |