| Notes |
| Date |
Text |
| 2011-12-05 15:20:52 | BUILDING PROVISO: | | | GATES CAN NOT BE PART OF A POOL BARRIER: | | | 424.1.3.1.9 ALL PUBLIC POOLS SHALL BE SURROUNDED | | | BY A MINIMUM 48 INCH (1219 MM) IN HEIGHT FENCE. | | | THE FENCE SHALL BE CONTINUOUS AROUND THE PERIMETER | | | OF THE POOL AREA THAT IS NOT OTHERWISE BLOCKED OR | | | OBSTRUCTED BY ADJACENT BUILDINGS OR STRUCTURES AND | | | SHALL ADJOIN WITH ITSELF OR ABUT TO THE ADJACENT | | | MEMBERS. | | | ACCESS THROUGH THE BARRIER OTHER THAN FROM DOORED EXITS | | | OF ADJACENT BUILDING(S) SHALL BE THROUGH SELF-CLOSING, | | | SELF-LATCHING LOCKABLE GATES OF 48 INCH (1219 MM) | | | MINIMAL HEIGHT WITH THE LATCH LOCATED NEAR THE TOP. | | | CONSIDERATION SHALL BE GIVEN TO THE U.S. CONSUMER | | | PRODUCT SAFETY COMMISSION (CPSC) PUB. NO. 362 | | | GUIDELINES. SAFETY COVERS THAT COMPLY WITH ASTM | | | F 1346 DO NOT SATISFY THIS REQUIREMENT. | | | |
|