| Plan Review Notes For Permit 11110570 |
| Permit Number |
11110570 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-12-12 09:53:06 | FBC PLUMBING 2007 REVIEW #1 | | | DENIED: | | | | | | 1. THE ADA STALLS DO NOT COMPLY WITH 11-4.17. A LAV IS | | | REQUIRED IN THE STALL WITH THE ACCESSABLE WC. PLEASE | | | SEE FIGURE 30(E) FOR DIMENSIONS. | | | 11-4.17 TOILET STALLS. 11-4.17.3 SIZE AND ARRANGEMENT. | | | EXCEPTION: NEW CONSTRUCTION. | | | (1) THE STANDARD ACCESSIBLE RESTROOM STALL SHALL | | | CONTAIN AN ACCESSIBLE LAVATORY WITHIN IT, THE SIZE OF | | | SUCH LAVATORY TO BE NOT LESS THAN 19 INCHES WIDE BY 17 | | | INCHES (483 MM BY 432 MM) DEEP, NOMINAL SIZE, AND WALL | | | MOUNTED. THE LAVATORY SHALL BE MOUNTED SO AS NOT TO | | | OVERLAP THE CLEAR FLOOR SPACE AREAS REQUIRED BY SECTION | | | 11-4.17 [SEE FIGURE 30(A) AND FIGURE 30(E)] AND TO | | | COMPLY WITH SECTION 11-4.19 OF THE CODE. SUCH | | | LAVATORIES SHALL BE COUNTED AS PART OF THE REQUIRED | | | FIXTURE COUNT FOR THE BUILDING. | | | | | | (2) THE ACCESSIBLE WATER CLOSET SHALL BE LOCATED IN THE | | | CORNER, DIAGONAL TO THE DOOR. | | | | | | | | | REVIEW BY | | | LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | PHONE # 805-6692 | | | EMAIL [email protected] | | | FAX # 805-6676 | | | |
|