2011-12-12 09:53:06FBC PLUMBING 2007 REVIEW #1
 DENIED:
  
 1. THE ADA STALLS DO NOT COMPLY WITH 11-4.17. A LAV IS
 REQUIRED IN THE STALL WITH THE ACCESSABLE WC. PLEASE
 SEE FIGURE 30(E) FOR DIMENSIONS.
 11-4.17 TOILET STALLS. 11-4.17.3 SIZE AND ARRANGEMENT.
 EXCEPTION: NEW CONSTRUCTION.
 (1) THE STANDARD ACCESSIBLE RESTROOM STALL SHALL
 CONTAIN AN ACCESSIBLE LAVATORY WITHIN IT, THE SIZE OF
 SUCH LAVATORY TO BE NOT LESS THAN 19 INCHES WIDE BY 17
 INCHES (483 MM BY 432 MM) DEEP, NOMINAL SIZE, AND WALL
 MOUNTED. THE LAVATORY SHALL BE MOUNTED SO AS NOT TO
 OVERLAP THE CLEAR FLOOR SPACE AREAS REQUIRED BY SECTION
 11-4.17 [SEE FIGURE 30(A) AND FIGURE 30(E)] AND TO
 COMPLY WITH SECTION 11-4.19 OF THE CODE. SUCH
 LAVATORIES SHALL BE COUNTED AS PART OF THE REQUIRED
 FIXTURE COUNT FOR THE BUILDING.
  
 (2) THE ACCESSIBLE WATER CLOSET SHALL BE LOCATED IN THE
 CORNER, DIAGONAL TO THE DOOR.
  
  