2011-12-19 13:39:33PLANS DENIED
 1) PROVIDE FRESH AIR CALCULATIONS ON THE PLANS.
 2) PROVIDE EQUIPMENT SCHEDULE ON THE PLANS.
 3) REFER TO SECTION 603.17 REGISTERS GRILLS AND
 DIFFUSERS.
 2007 FBC (M)
 4) PROVIDE CFM FOR EXHAUST FANS ON THE PLANS.
 5) DUCT DETECTORS MUST BE TIED INTO THE FIRE ALARM
 PANEL.