| 2011-11-30 13:24:04 | 1551 FORUM PLACE - SUITE #200 |
| | PERMIT #11110570 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | PROVIDE SUITE NUMBER IN ADDRESS TITLEBLOCK. |
| | |
| | PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY |
| | RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING |
| | NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM |
| | WWW.KNOXBOX.COM. |
| | |
| | SHEET A-2 INDICATES SPECIAL NEEDS STUDENTS. WILL THIS |
| | FACILITY BE FUNCTIONING MORE AS AN EDUCATIONAL |
| | OCCUPANCY OR DAY CARE OCCUPANCY? |
| | |
| | INDICATE THE OCCUPANT LOAD AND AGE GROUPS OF THE DAY |
| | CARE CLIENTS. |
| | |
| | EACH NEW SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE |
| | PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING |
| | FIRE/SMOKE BARRIER-PROTECT ALL OPENINGS. CHARACTERS |
| | SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN |
| | WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 |
| | FEET ON CENTER. |
| | |
| | PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY SHALL |
| | BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE. |
| | |
| | SPECIAL PROTECTIVE COVERS FOR ALL ELECTRICAL |
| | RECEPTACLES SHALL BE INSTALLED IN ALL AREAS OCCUPIED BY |
| | CLIENTS. |
| | |
| | THE EXISTING EXIT ACCESS CORRIDOR SHALL PROVIDE ACCESS |
| | TO NOT LESS THAN TWO APPROVED EXITS. |
| | |
| | CORRIDOR DOOR #3 AND #5 SHALL SWING IN THE DIRECTION OF |
| | EGRESS AND BE EQUIPPED WITH FIRE EXIT HARDWARE. |
| | |
| | CORRIDOR DOOR #1 SHALL BE EQUIPPED WITH PANIC HARDWARE. |
| | |
| | NONE OF THE DOORS LOCATED IN THE ONE-HOUR FIRE BARRIERS |
| | ARE INDICATED AS HAVING A FIRE RATING OR EQUIPPED WITH |
| | CLOSERS. |
| | |
| | CLARIFY THE FUNCTION OF THE BREAKOUT ROOM. |
| | |
| | SHEET A-2 INDICATES SPECIAL NEEDS STUDENTS AND |
| | ACCESS-CONTROLLED EGRESS. PLEASE PROVIDE MORE DETAILED |
| | INFORMATION. ACCESS-CONTROLLED EGRESS SHALL COMPLY WITH |
| | ALL THE REQUIREMENTS OF NFPA 101. |
| | |
| | INDICATE THE LOCATION OF ANY DUCT SMOKE DETECTORS OR |
| | FIRE DAMPERS. |
| | |
| | PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH |
| | EXIT SIGNS. |
| | |
| | ARTWORK AND TEACHING MATERIALS ATTACHED TO THE WALLS |
| | SHALL NOT EXCEED 20 PERCENT OF THE INDIVIDUAL WALL |
| | AREA. |
| | |
| | AN EMERGENCY PLAN TO BE DEVELOPED AND POSTED IN |
| | BUILDING PRIOR TO OCCUPANCY. |
| | |
| | EMERGENCY EGRESS DRILLS SHALL BE CONDUCTED MONTHLY. ALL |
| | DRILLS SHALL BE SOUNDED ON THE FIRE ALARM SYSTEM. |
| | |
| | FIRE PREVENTION INSPECTIONS SHALL BE CONDUCTED MONTHLY |
| | BY A TRAINED SENIOR MEMBER OF THE STAFF, AFTER WHICH A |
| | COPY OF THE LATEST INSPECTION REPORT SHALL BE POSTED IN |
| | A CONSPICUOUS PLACE IN THE DAY-CARE FACILITY. IT SHALL |
| | BE THE DUTY OF THE STAFF TO INSPECT ALL EXITS DAILY TO |
| | ENSURE THAT ALL DOORS AND EXIT PATHS ARE MAINTAINED |
| | CLEAR OF OBSTRUCTIONS. |
| | |
| | SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE |
| | INSTALLATION OR MODIFICATION OF THE FIRE ALARM SYSTEM. |
| | |
| | WESLEY JOLIN |
| | WEST PALM BEACH FIRE RESCUE |
| | FIRE & LIFE SAFETY PLAN REVIEW |