| Plan Review Notes For Permit 11110570 |
| Permit Number |
11110570 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-12-05 16:06:27 | 11110570 | | | 1551 FORUM PL #200 | | | RENOVATION FOR DAY CARE | | | | | | PROVIDE A DEDICATED SAFE WORKING SPACE FOR ELECTRICAL | | | PANEL BOARD A AND B. ARE THESE PANELS NEW OR EXISTING? | | | NEC 110.26 | | | ALL RECEPTACLES SHALL BE TAMPER RESISTANT. NEC 406.14 | | | SPECIFY ON THE PLANS HOW THE LIGHTING WILL BE | | | CONTROLLED USING MOTION SENSORS OR SIMILAR TECHNIQUES | | | AS REQUIRED BY THE FLORIDA BUILDING CODE. SPACE CONTROL | | | FBC 13-415 ABC.1.2; ADDITIONAL CONTROLS 13-415.ABC.1.3, | | | EXISTING BUILDING 711.1 | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|