2011-12-01 13:42:03BUILDING PLAN REVIEW
 PERMIT: 11110570
 ADD: 1551 FORUM PLACE # 200
 CONT: LTL BUILDERS, INC
 TEL: (561)628-9753
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET C-1 CODE TABULATION:
 1A) NOTE INDICATES CODE SECTIONS 304.1/ 305.1. 304.1 IS
 BUSINESS OCCUPANCIES AND 305.1 IS EDUCATIONAL
 OCCUPANCIES IS THIS THE CORRECT OCCUPANCIES OR SHOULD
 THE CODE SECTION BE 313.1 DAYCARE AS LISTED BELOW IN
 THE CODE ANALYSIS?
  
 1B) PLEASE PROVIDE HOW MANY STORIES THIS BUILDING IS,
 AND IF SUITE 200 IS LOCATED ABOVE THE GRADE FLOOR SINCE
 A DAYCARE ON THE SECOND FLOOR WOULD REQUIRE SMOKE
 BARRIERS
 FOR CLIENTS 24 MONTHS OR LESS OR INCAPABLE OF SELF
 PRESERVATION.
  
 1C) A NOTE ON SHEET A2 INDICATES THE CLASSROOMS ARE FOR
 SPECIAL NEEDS STUDENTS, TWO QUESTIONS ARISE,
 1) WHAT ARE THE AGES OF THESE STUDENTS?
 2) ARE THE STUDENTS ABLE OR INCAPABLE OF SELF
 PRESERVATION? IF THE CLASSROMMS ARE ON THE SECOND FLOOR
 REQUIRING SMOKE BARRIERS?
  
 1D) SHEET A1 THE CODE ANYLSIS DOES STATE THE BUILDING
 IS NON-SPRINKLERED BUT SHEET A2 NOTE 2 INDICATES USE OF
 FIRE SPRINKLERS? ADDITIONAL INFORMATION REQUIRED
 106.1.2.
  
 2) PLEASE NOTE THAT SHEET A2 DOOR SCHEDULE, NONE OF THE
 DOORS WITHIN THE 1 HOUR RATED CORRIDOR SHOW ANY FIRE
 RATING FBC-B TABLE 1017.1 REQUIRES A 1 HOUR FIRE RATED
 CORRIDOR. FBC-B TABLE 715.4 INDICATES FIRE RATED
 PROTECTIVE OPENINGS.
  
 3) SHEET A2 THE FRONT ENTRY DOOR DOES HAVE A NOTE TO
 REVERSE THE SWING OF THE DOOR SO IT WILL BE IN THE
 DIRECTION OF TRAVEL COMPLING WITH FBC-B 1008.1.2, HOW
 EVER THE BACK ENTRY DOOR # 5 AND CORRIDOR DOOR # 3 WILL
 ALSO NEED TO REVERSE THE SWING IN THE DIRECTION OF
 TRAVEL PER 1008.1.2.
  
 4) SHEET A2 THE STORAGE ROOM PLEASE PROVIDE TYPES OF
 ITEMS TO BE STORED WITHIN THIS ROOM. THE GENERAL RULE
 FOR INCIDENTIAL USE AREAS FBC-B T 508.2 WILL NOT
 REQUIRE STORAGE ROOMS LESS THAN 100 SQ FT TO BE FIRE
 RATED BUT THE MORE RESTRICTIVE FBC-B 436.1 MAY OR MAY
 NOT REQUIRE FIRE RATING DEPENDING ON USAGE.
  
 5) SHEET A2 DOOR SCHEDULE WILL NEED TO PROVIDE
 ADDITIONAL INFORMATION TO COMPLY WITH THE FOLLOWING
 CODE ARTICLES: FBC-B 436.2, 536.3 & 436.4.
  
 6) SHEET A2 INDICATES THE USE OF 5'-0" CORRIDORS,
 PLEASE REVIEW FBC-B 1017.2 EXCEPTION 4 REQUIRING 72"
 FOR EDUCATIONAL , AGAIN DEPENDING ON THE AGE OF THE
 CHILDREN THIS MAY BE A EDUCATIONAL USAGE REQUIRING THE
 WIDER CORRIDORS FOR OCCUPANT LOAD OVER 100 OCCUPANTS.
  
 7) SHEET A2 DOOR SCHEDULE DOES NOT PROVIDE TYPE OF
 HARDWARE TO BE USED ON DOORS PLEASE SEE FBC-B 1034.1.1
 FOR PANIC HARDWARE.
  
 8) SHEET A2 DOES INDICATE TWO EXITS THAT CONNECT TO A
 COMMON CORRIDOR. FBC-B 1034.2.1 REQUIRES THE TWO EXITS
 IF LEADING INTO A COMMON CORRIDOR TO LEAD TO SEPERATE
 EXITS LOCATED IN OPPOSITE DIRECTIONS.
  
 9) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]