| 2011-12-01 13:42:03 | BUILDING PLAN REVIEW |
| | PERMIT: 11110570 |
| | ADD: 1551 FORUM PLACE # 200 |
| | CONT: LTL BUILDERS, INC |
| | TEL: (561)628-9753 |
| | |
| | 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) SHEET C-1 CODE TABULATION: |
| | 1A) NOTE INDICATES CODE SECTIONS 304.1/ 305.1. 304.1 IS |
| | BUSINESS OCCUPANCIES AND 305.1 IS EDUCATIONAL |
| | OCCUPANCIES IS THIS THE CORRECT OCCUPANCIES OR SHOULD |
| | THE CODE SECTION BE 313.1 DAYCARE AS LISTED BELOW IN |
| | THE CODE ANALYSIS? |
| | |
| | 1B) PLEASE PROVIDE HOW MANY STORIES THIS BUILDING IS, |
| | AND IF SUITE 200 IS LOCATED ABOVE THE GRADE FLOOR SINCE |
| | A DAYCARE ON THE SECOND FLOOR WOULD REQUIRE SMOKE |
| | BARRIERS |
| | FOR CLIENTS 24 MONTHS OR LESS OR INCAPABLE OF SELF |
| | PRESERVATION. |
| | |
| | 1C) A NOTE ON SHEET A2 INDICATES THE CLASSROOMS ARE FOR |
| | SPECIAL NEEDS STUDENTS, TWO QUESTIONS ARISE, |
| | 1) WHAT ARE THE AGES OF THESE STUDENTS? |
| | 2) ARE THE STUDENTS ABLE OR INCAPABLE OF SELF |
| | PRESERVATION? IF THE CLASSROMMS ARE ON THE SECOND FLOOR |
| | REQUIRING SMOKE BARRIERS? |
| | |
| | 1D) SHEET A1 THE CODE ANYLSIS DOES STATE THE BUILDING |
| | IS NON-SPRINKLERED BUT SHEET A2 NOTE 2 INDICATES USE OF |
| | FIRE SPRINKLERS? ADDITIONAL INFORMATION REQUIRED |
| | 106.1.2. |
| | |
| | 2) PLEASE NOTE THAT SHEET A2 DOOR SCHEDULE, NONE OF THE |
| | DOORS WITHIN THE 1 HOUR RATED CORRIDOR SHOW ANY FIRE |
| | RATING FBC-B TABLE 1017.1 REQUIRES A 1 HOUR FIRE RATED |
| | CORRIDOR. FBC-B TABLE 715.4 INDICATES FIRE RATED |
| | PROTECTIVE OPENINGS. |
| | |
| | 3) SHEET A2 THE FRONT ENTRY DOOR DOES HAVE A NOTE TO |
| | REVERSE THE SWING OF THE DOOR SO IT WILL BE IN THE |
| | DIRECTION OF TRAVEL COMPLING WITH FBC-B 1008.1.2, HOW |
| | EVER THE BACK ENTRY DOOR # 5 AND CORRIDOR DOOR # 3 WILL |
| | ALSO NEED TO REVERSE THE SWING IN THE DIRECTION OF |
| | TRAVEL PER 1008.1.2. |
| | |
| | 4) SHEET A2 THE STORAGE ROOM PLEASE PROVIDE TYPES OF |
| | ITEMS TO BE STORED WITHIN THIS ROOM. THE GENERAL RULE |
| | FOR INCIDENTIAL USE AREAS FBC-B T 508.2 WILL NOT |
| | REQUIRE STORAGE ROOMS LESS THAN 100 SQ FT TO BE FIRE |
| | RATED BUT THE MORE RESTRICTIVE FBC-B 436.1 MAY OR MAY |
| | NOT REQUIRE FIRE RATING DEPENDING ON USAGE. |
| | |
| | 5) SHEET A2 DOOR SCHEDULE WILL NEED TO PROVIDE |
| | ADDITIONAL INFORMATION TO COMPLY WITH THE FOLLOWING |
| | CODE ARTICLES: FBC-B 436.2, 536.3 & 436.4. |
| | |
| | 6) SHEET A2 INDICATES THE USE OF 5'-0" CORRIDORS, |
| | PLEASE REVIEW FBC-B 1017.2 EXCEPTION 4 REQUIRING 72" |
| | FOR EDUCATIONAL , AGAIN DEPENDING ON THE AGE OF THE |
| | CHILDREN THIS MAY BE A EDUCATIONAL USAGE REQUIRING THE |
| | WIDER CORRIDORS FOR OCCUPANT LOAD OVER 100 OCCUPANTS. |
| | |
| | 7) SHEET A2 DOOR SCHEDULE DOES NOT PROVIDE TYPE OF |
| | HARDWARE TO BE USED ON DOORS PLEASE SEE FBC-B 1034.1.1 |
| | FOR PANIC HARDWARE. |
| | |
| | 8) SHEET A2 DOES INDICATE TWO EXITS THAT CONNECT TO A |
| | COMMON CORRIDOR. FBC-B 1034.2.1 REQUIRES THE TWO EXITS |
| | IF LEADING INTO A COMMON CORRIDOR TO LEAD TO SEPERATE |
| | EXITS LOCATED IN OPPOSITE DIRECTIONS. |
| | |
| | 9) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |