| Plan Review Notes For Permit 11110560 |
| Permit Number |
11110560 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2012-01-06 17:45:01 | BUILDING REVISION COMMENTS: | | | | | | 1- A) LOAD SCHEDULE INFORMATION ON SHEET C-1 AND LOAD | | | SCHEDULE INFORMATION ON THE TRUSS DRAWINGS SUBMITTED | | | DON'T MATCH. PLEASE COORDINATE INFORMATION. LIVE LOAD | | | SPECIFICATIONS AND DEAD LOAD SPECIFICATIONS DON'T | | | MATCH. REVISE AS REQUIRED TO MATCH. | | | | | | B) ENGINEER OF RECORD TO REVIEW AND APPROVE TRUSS | | | DRAWINGS PRIOR TO SUBMITTAL TO THIS OFFICE. | | | | | | 2- PLEASE PROVIDE REVISED PLUMBING RISER DIAGRAM THAT | | | MATCHES FLOOR PLAN. DIAGRAM SUBMITTED IS MISSING THE | | | KITCHEN ISLAND SINK AND THE KITCHEN SINK IS A DOUBLE | | | SINK NOT SINGLE. REVISE AS REQUIRED. | | | | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 | | | | | | |
|