| 2011-11-30 16:12:52 | BUILDING REVISION COMMENTS: |
| | |
| | 1- LOAD SCHEDULE INFORMATION ON SHEET C-1 AND LOAD |
| | SCHEDULE INFORMATION ON THE TRUSS DRAWINGS DON'T MATCH. |
| | PLEASE COORDINATE INFORMATION. NOTE: LOADS NEED TO |
| | COMPLY WITH TABLE R301.5 INCLUDING THE LIVE LOADS FOR |
| | LIMITED STORAGE. PLEASE, SHOW THAT TRUSSES FOR LIMITED |
| | STORAGE AT GARAGE AREA ARE DESIGNED FOR THE 20PSF LIVE |
| | LOAD AS REQUIRED BY TABLE R301.5. |
| | |
| | 2- PLEASE PROVIDE COMPLETE INFORMATION FOR SCREEN |
| | ENCLOSURE ON COVERED PATIO #2 UNDER A SEPARATE PERMIT. |
| | NO INFORMATION WAS SUBMITTED YET. |
| | |
| | 3- PLEASE PROVIDE REVISED PLUMBING RISER DIAGRAM TO |
| | INCLUDE THE NEW SINK SHOWN ON COVERED PATIO #2. |
| | |
| | 4- A) PROVIDE COMPLETE ICYNENE SPECIFICATIONS AS |
| | SPECIFIED ON PLANS. |
| | |
| | B) ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | THIS SPECIFICATIONS. SEC. 106.3.3 CITY AMENDMENTS. |
| | |
| | 5- A) PLEASE REVISE THE ENERGY CALCULATIONS. REVISE THE |
| | CEILING R VALUE ON ITEM #10. NEED R-19 MINIMUM AS |
| | REQUIRED BY SEC. N1104.AB.1. NOTE: UNVENTED ATTIC AND |
| | R-INSULATION ARE TWO DIFFERENT THINGS. CEILING |
| | INSULATION IS ALWAYS REQUIRED. |
| | |
| | B) OWNER/AGENT TO SIGN AND DATE THE BOTTOM OF THE FORM |
| | ALSO. |
| | |
| | 6- PLEASE ADDRESS ZONING COMMENTS NOTED ON REVISION |
| | #11080512 TO AVOID ANY CONFLICTS OR DELAYS. CONTACT |
| | LINDA FRANCO AT (561)822-1443. |
| | |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561)805-6712 |
| | |
| | |