| Plan Review Notes For Permit 11110551 |
| Permit Number |
11110551 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2011-12-22 13:21:21 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY MECHANICAL | | | | | | 1) FLORIDA STATUTE 471.003 (2) (H) ALLOWS MECHANICAL | | | CONTRACTORS TO DESIGN MECHANICAL SYSTEMS WHICH HE | | | INSTALLS BY VIRTUE OF A LICENSE ISSUED UNDER CHAPTER | | | 489. HOWEVER, THE CONTRACTOR LISTED ON THE PLANS | | | (PREFERRED A/C & MECH INC) IS NOT THE SAME AS THE ONE | | | THAT SIGNED THE PERMIT APPLICATION (LINDSTROM A/C | | | INC.). THEREFORE, THE PLANS MUST BE SIGNED AND SEALED | | | OR THE SAME CONTRACTOR THAT DOES THE PLANS MUST INSTALL | | | THE SYSTEM. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|