| Plan Review Notes For Permit 11110531 |
| Permit Number |
11110531 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-12-12 16:56:30 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY BUILDING | | | | | | 1) THE BUILDING CODE DATA ON SHEET A.01 IS NOT CORRECT. | | | THE CURRENT CODE REFERENCED CODES ARE THE 2007 FLORIDA | | | BUILDING CODE RESIDENTIAL WITH 2009 REVISIONS, 2007 FBC | | | PLUMBING, THE 2007 FBC MECHANICAL AND THE 2008 NATIONAL | | | ELECTRICAL CODE (N.E.C.). PLEASE CORRECT. SEE FBCR | | | CHAPTER 43. | | | | | | 2) THE STRUCTURE IS LOCATED APPROXIMATELY 600 FEET FROM | | | THE INTER-COASTAL WATER WAY. THEREFORE, THE EXPOSURE | | | CATEGORY IS C PER FBCR 301.2.1.4.3. | | | | | | 3) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE NEW | | | SINGLE HUNG WINDOW IS EXPIRED. PLEASE SUBMIT TWO COPIES | | | OF CURRENT PRODUCT APPROVALS AS REQUIRED BY DCA RULE | | | 9N-3. REVISE PLAN TO REFERENCE THE NEW NOA NUMBER. | | | | | | 4) THE PLANS INDICATE THAT THE NEW KITCHEN WINDOWS ARE | | | CONNECTED BY A STRUCTURAL MULLION. PLEASE SUBMIT TWO | | | COPIES OF CURRENT PRODUCT APPROVALS FOR THE STRUCTURAL | | | MULLION AS REQUIRED BY DCA RULE 9N-3. | | | | | | 5) PROVIDE A WINDOW BUCK FASTENING DETAIL SHOWING | | | COMPLIANCE WITH FBC R613.6.1.1. | | | | | | 6) SPECIFY THE COMPONENT AND CLADDING PRESSURES FOR THE | | | NEW WINDOWS ON THE PLANS. SEE FBC R301.2.1. | | | | | | 7) SHOW COMPLIANCE WITH FBC R313.2.1 AND R313.4 FOR | | | REQUIRED SMOKE AND CARBON MONOXIDE ALARMS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|