Plan Review Notes
Plan Review Notes For Permit 11110531
Permit Number 11110531
Review Stop B
Sequence Number 1
Notes
Date Text
2011-12-12 16:56:302007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) THE BUILDING CODE DATA ON SHEET A.01 IS NOT CORRECT.
 THE CURRENT CODE REFERENCED CODES ARE THE 2007 FLORIDA
 BUILDING CODE RESIDENTIAL WITH 2009 REVISIONS, 2007 FBC
 PLUMBING, THE 2007 FBC MECHANICAL AND THE 2008 NATIONAL
 ELECTRICAL CODE (N.E.C.). PLEASE CORRECT. SEE FBCR
 CHAPTER 43.
  
 2) THE STRUCTURE IS LOCATED APPROXIMATELY 600 FEET FROM
 THE INTER-COASTAL WATER WAY. THEREFORE, THE EXPOSURE
 CATEGORY IS C PER FBCR 301.2.1.4.3.
  
 3) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE NEW
 SINGLE HUNG WINDOW IS EXPIRED. PLEASE SUBMIT TWO COPIES
 OF CURRENT PRODUCT APPROVALS AS REQUIRED BY DCA RULE
 9N-3. REVISE PLAN TO REFERENCE THE NEW NOA NUMBER.
  
 4) THE PLANS INDICATE THAT THE NEW KITCHEN WINDOWS ARE
 CONNECTED BY A STRUCTURAL MULLION. PLEASE SUBMIT TWO
 COPIES OF CURRENT PRODUCT APPROVALS FOR THE STRUCTURAL
 MULLION AS REQUIRED BY DCA RULE 9N-3.
  
 5) PROVIDE A WINDOW BUCK FASTENING DETAIL SHOWING
 COMPLIANCE WITH FBC R613.6.1.1.
  
 6) SPECIFY THE COMPONENT AND CLADDING PRESSURES FOR THE
 NEW WINDOWS ON THE PLANS. SEE FBC R301.2.1.
  
 7) SHOW COMPLIANCE WITH FBC R313.2.1 AND R313.4 FOR
 REQUIRED SMOKE AND CARBON MONOXIDE ALARMS.
  