| Plan Review Notes For Permit 11110523 |
| Permit Number |
11110523 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-12-06 14:52:04 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY BUILDING | | | | | | 1) SPECIFY THE STRUCTURAL DESIGN CRITERIA ON THE PLANS | | | AS REQUIRED BY CITY AMENDMENTS 106.3.5.4. SEE FBC | | | R301.1 (THE WIND SPEED IS 140 MPH AND THE EXPOSURE | | | CATEGORY IS C.) | | | | | | 2) THE OWNER/AGENT IS REQUIRED TO SIGN THE ENERGY | | | CALCULATION FORM BY 2007 FBCR ENERGY AMENDMENTS SECTION | | | N1100.2.2. | | | | | | 3) THE PRODUCT APPROVALS (NOA 08-1112.09) THAT WERE | | | SUBMITTED FOR THE PGT FIXED GLASS WINDOWS ARE FOR NON - | | | IMPACT RATED GLASS. THEREFORE, HURRICANE PANELS WILL BE | | | REQUIRED FOR IMPACT PROTECTION AS REQUIRED BY FBC | | | R301.2.1.2. SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR | | | THE IMPACT PROTECTION DEVICES AND INSTALLATION | | | SCHEDULES. | | | | | | 4) INSTALL SMOKE ALARMS IN COMPLIANCE WITH FBC | | | R313.2.1. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|