| Plan Review Notes For Permit 11110506 |
| Permit Number |
11110506 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2012-01-19 16:07:22 | RE-SUBMITTAL BUILDING REVIEW COMMENTS. | | | | | | 1- SHEET #6.0: WHAT'S "FAST DRY TFS INSULATION" THAT | | | WAS SPECIFIED FOR THE CEILING INSULATION. PROVIDE | | | MANUFACTURER SPECIFICATIONS. INSULATION NEED TO COMPLY | | | WITH SEC. R316. | | | | | | 2- REVISE THE ENERGY CALCULATIONS: | | | A) INFORMATION ON ITEM #6A WAS NOT ENTERED. THIS | | | INFORMATION IS REQUIRED. | | | | | | B) INFORMATION ON ITEM #6B NEED TO BE REVISED. THE | | | VALUE FOR THE SHGC NEEDS TO BE THE SAME VALUE AS SHOWN | | | ON TABLE 11B-1 (0.35) ON SECOND PAGE OR BETTER. | | | INFORMATION SUBMITTED SHOWS .78. THE LOWER THE NUMBER | | | THE BETTER PERFORMANCE. REVISE AS REQUIRED. | | | | | | C) OWNER/AGENT NEEDS TO SIGN AND DATE BOTTOM OF FORM | | | ALSO. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|