Plan Review Notes
Plan Review Notes For Permit 11110506
Permit Number 11110506
Review Stop B
Sequence Number 1
Notes
Date Text
2011-12-07 13:34:11RESIDENTIAL (R3) ADDITION BUILDING REVIEW COMMENTS.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- PLEASE TAKE DRAWINGS TO THE PALM BEACH COUNTY
 BUILDING (2300 N. JOG RD.) TO CHECK IF IMPACT FEES ARE
 DUE. BRING BACK STAMPED PLANS AND COPY OF PAID RECEIPT
 IF FEES ARE DUE.
  
 2- PLEASE PROVIDE PRODUCT APPROVALS (2 COPIES) AS
 REQUIRED BY DCA RULE 9N-3 FOR:
 A) SINGLE HUNG WINDOWS. SINGLE HUNG NOA 07-0717.05
 SUBMITTED WAS SUPERSEDED BY MIAMI-DADE. PLEASE VISIT
 THE MIAMI-DADE WEBSITE AND DOWNLOAD CURRENT NOA.
  
 B) ALL SIMPSON STRUCTURAL COMPONENTS SPECIFIED BY THE
 ENGINEER ON THE SECTIONS AND DETAILS.
 ***NOTE: PROVIDE ONLY THE PRODUCT APPROVAL COVER PAGE
 AND PAGE SHOWING THE CONNECTOR. OR, ENGINEER MAY
 SPECIFY PRODUCT APPROVAL NUMBER (2007 CODE VERSION) ON
 DRAWINGS SUBMITTED.
  
 3-ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALS AS REQUIRED BY SEC. 106.3.3.
  
 4- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. SEC. 108.3 CITY AMENDMENTS. VALUATION TO INCLUDE
 ALL LABOR, MATERIALS, AND ENGINEER FEES. PLEASE UPDATE
 VALUATION AS REQUIRED.
  
 5- PLEASE, PROVIDE RECORDED NOTICE OF COMMENCEMENT AS
 REQUIRED BY CHAPTER 713 FLORIDA STATUTES.
  
 6- SHEET 2.0:
 A) WINDOW SCHEDULE CALLS WINDOW NO 1 TO BE SH-24.
 ACCORDING TO THE WIDTH & HEIGHT SPECIFIED THE CORRECT
 WINDOW TYPE IS SH25. PLEASE REVISE AS REQUIRED.
  
 B) R-19 INSULATION DOESN'T FIT IN A 2X4 WALL. REVISE
 WALL LEGEND. ALSO, COORDINATE WITH THE REVISED ENERGY
 CALCULATIONS.
  
 7- SHEET 6.0:
 A) WALL SECTIONS DON'T SHOW ROOF VENTILATION. PLEASE
 SPECIFY ROOF VENTILATION. SEC. R806.1. COORDINATE WITH
 THE REVISED ENERGY CALCULATIONS.
  
 B) WALL SECTIONS SHOW R19 INSULATION ON THE ROOF. R-19
 BATT INSULATION DOESN'T FIT ON THE 3X6 ROOF RAFTERS.
 COORDINATE WITH THE REVISED ENERGY CALCULATIONS.
  
 C) PLEASE COORDINATE THE R-VALUE SPECIFIED FOR THE
 WALLS ON WALL SECTIONS. PLEASE COORDINATE WITH THE
 REVISED ENERGY CALCULATIONS.
  
 8- PLEASE REVISE THE ENERGY CALCULATIONS SUBMITTED:
 A) TABLE 11B-1 ON THE SECOND PAGE REQUIRES R-30
 INSULATION ON THE CEILING. ITEM #10 ON FIRST PAGE
 SPECIFIES R-19. NEED TO PROVIDE R-30 MIN. (ALSO, CHECK
 SIZE OF RAFTERS ON SHEET 6.0).
  
 ***NOTE: FORM 1100B-08 IS A PRESCRIPTIVE METHOD AND
 NEED TO INSTALL THE MINIMUM REQUIREMENTS SHOWN ON TABLE
 11B-1. YOU MAY TRY TO SEE IF USING FORM 1100A-08 WILL
 COMPLY.
  
 B) COMPLETE ALL THE INFORMATION ON THE FORM ON ITS
 ENTIRETY. SEE ITEMS 4, 6B, 6C, 8A. ALSO, THE SQUARE
 FOOTAGE FOR ITEM 9A IS INCORRECT.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
  
  
  