| 2011-11-21 16:02:11 | REROOF REVISION BUILDING REVIEW COMMENTS. | | | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | | | 1- ENGINEER TO PROVIDE RAS 117 CALCULATIONS FOR THE | | | CORNER AREAS. ACCORDING TO SEC. 10.4.5 OF RAS 117 ALL | | | CALCULATIONS NEED TO BE ROUNDED DOWN TO THE NEXT WHOLE | | | NUMBER NOT ROUNDED UP. MY CALCULATIONS SHOW THAT | | | FASTENER SPACING FOR CORNER AREAS IS LESS THAN 8" O.C.. | | | PLEASE REVISE CALCULATIONS AS REQUIRED. | | | | | | 2- FLAT ROOF PRODUCT APPROVAL SUBMITTED IS DIFFERENT | | | FROM THE ONE APPROVED AT THE TIME OF PERMIT ISSUANCE. | | | PLEASE, PROVIDE COMPLETE FLORIDA PRODUCT APPROVAL. ONLY | | | PAGE 5 WAS SUBMITTED AT THIS TIME. | | | | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|