2012-02-22 12:34:368289 OKEECHOBEE BOULEVARD
 PERMIT #11110429
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO - SEPARATE PLANS/PERMIT WILL BE SUBMITTED
 TO CITY TO ADDRESS CIVIL PLAN REVIEW COMMENTS
 BELOW*****
  
  
 CIVIL WATER SHEET 5 OF 7: THE FIRE HYDRANTS ARE LOCATED
 ON A DEAD-END WATER MAIN. PROVIDE LOOPED SYSTEM.
  
 CIVIL WATER SHEET 3 OF 9: BOTH THE FIRE WATER AND
 DOMESTIC WATER ARE SUPPLIED BY A COMMON 4-INCH MAIN.
 PROVIDE INDEPENDENT FIRE/DOMESTIC TAPS INTO THE 8-INCH
 FEED MAIN.
  
 CIVIL WATER SHEET 4 OF 9: FIRE HYDRANTS SHALL BE
 PROVIDED WITH CLEARANCES OF 7'-6" TO THE FRONT AND
 SIDES AND 4' TO THE BACKSIDE. THE PARKING SPACES
 ADJACENT TO THE FIRE HYDRANTS APPEAR TO ENCROACH UPON
 THE REQUIRED CLEARANCE.
  
 SHEET LP2: CONFIRM PLUMBAGO LANDSCAPE TO BE LOCATED
 OUTSIDE THE 7'-6" CLEAR SPACE RADIUS OF THE NEW FIRE
 HYDRANT.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW