2012-01-18 16:17:068289 OKEECHOBEE BOULEVARD
 PERMIT #11110429
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET SP1: PROVIDE PAINTED CURB MARKINGS AND
 FREESTANDING SIGNS MARKING THE FIRE LANE AROUND PARKING
 LOT WHERE NO PARKING STALLS ARE LOCATED. FIRE LANES
 SHALL BE MARKED WITH FREESTANDING SIGNS READING, "FIRE
 LANE - NO PARKING BY ORDER OF THE FIRE DEPARTMENT"
 SIGNS SHALL BE 12" X 18" WITH A WHITE BACKGROUND AND
 RED LETTERS AND SHALL BE A MAXIMUM OF SEVEN FEET IN
 HEIGHT TO THE BOTTOM OF THE SIGN. SIGNS SHALL BE WITHIN
 SIGHT OF THE TRAFFIC FLOW AND BE SPACED A MAXIMUM OF 60
 FEET APART.
  
 CIVIL WATER SHEET 5 OF 7: THE FIRE HYDRANTS ARE LOCATED
 ON A DEAD-END WATER MAIN. PROVIDE LOOPED SYSTEM.
  
 CIVIL WATER SHEET 3 OF 9: BOTH THE FIRE WATER AND
 DOMESTIC WATER ARE SUPPLIED BY A COMMON 4-INCH MAIN.
 PROVIDE INDEPENDENT FIRE/DOMESTIC TAPS INTO THE 8-INCH
 FEED MAIN.
  
 CIVIL WATER SHEET 4 OF 9: FIRE HYDRANTS SHALL BE
 PROVIDED WITH CLEARANCES OF 7?-6? TO THE FRONT AND
 SIDES AND 4? TO THE BACKSIDE. THE PARKING SPACES
 ADJACENT TO THE FIRE HYDRANTS APPEAR TO ENCROACH UPON
 THE REQUIRED CLEARANCE.
  
 SHEET LP2: CONFIRM PLUMBAGO LANDSCAPE TO BE LOCATED
 OUTSIDE THE 7'-6" CLEAR SPACE RADIUS OF THE NEW FIRE
 HYDRANT.
  
 SHEET A4: PLANS INDICATE BATTERY BACK-UP FOR
 ELECTROMAGNETIC LOCK; CONFIRM LOSS OF POWER TO THE
 ACCESS CONTROL SYSTEM UNLOCKS THE DOORS IN THE
 DIRECTION OF EGRESS. DOORS SHALL BE FAIL SAFE.
  
 SHEET A4: DOOR MARKER "A" INDICATES AN ELECTROMAGNETIC
 LOCK AND AN EXTERIOR KEY OPERATED CYLINDER. INDICATE
 HOW THE KEY OPERATED CYLINDER WILL BE UNLOCKED FROM THE
 EGRESS SIDE.
 NOTE: THE LOCK/LATCH RELEASING MECHANISM ON ALL DOORS
 SHALL OPEN THE DOOR WITH NOT MORE THAN ONE RELEASING
 OPERATION.
  
 SHEET A4: LOBBY DOOR "B" MAY BE SUBJECT TO MORE THAN
 100 PERSONS AND WILL NEED TO BE RELEASED BY PANIC
 HARDWARE.
  
 SHEET FP1: DRAWING IS NOT SIGNED/SEALED BY A
 PROFESSIONAL ENGINEER.
  
 SHEET FP1:THE FIRE DEPARTMENT CONNECTION SHALL BE
 LOCATED NEAR FIRE DEPARTMENT ACCESS POINT. RECOMMEND A
 FREE STANDING CONNECTION NEAR THE NEW FIRE HYDRANT OR A
 WALL MOUNTED CONNECTION AT THE NORTHEAST OF THE
 BUILDING.
  
 SHEET FP1: PROVIDE CHAIN WITH LOCK AND TAMPER SWITCHES
 FOR SUPERVISING THE BACKFLOW PREVENTER IN THE OPEN
 POSITION.
  
 SHEET FA1: FIRE SPRINKLER FLOW SWITCH SHALL INITIATE A
 GENERAL FIRE ALARM CONDITION.
  
 SHEET FA1: PER LOCAL CODE AMENDMENTS, DUCT SMOKE
 DETECTORS SHALL INITIATE A GENERAL FIRE ALARM
 CONDITION.
  
 SHEET FA1: PROVIDE MONITOR MODULES FOR SUPERVISING THE
 FIRE SPRINKLER BACKFLOW PREVENTER.
  
 SHEET FA1: PROVIDE SMOKE DETECTION FOR GYM AREA AND
 HALL #6.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW