| 2012-01-18 16:17:06 | 8289 OKEECHOBEE BOULEVARD |
| | PERMIT #11110429 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | SHEET SP1: PROVIDE PAINTED CURB MARKINGS AND |
| | FREESTANDING SIGNS MARKING THE FIRE LANE AROUND PARKING |
| | LOT WHERE NO PARKING STALLS ARE LOCATED. FIRE LANES |
| | SHALL BE MARKED WITH FREESTANDING SIGNS READING, "FIRE |
| | LANE - NO PARKING BY ORDER OF THE FIRE DEPARTMENT" |
| | SIGNS SHALL BE 12" X 18" WITH A WHITE BACKGROUND AND |
| | RED LETTERS AND SHALL BE A MAXIMUM OF SEVEN FEET IN |
| | HEIGHT TO THE BOTTOM OF THE SIGN. SIGNS SHALL BE WITHIN |
| | SIGHT OF THE TRAFFIC FLOW AND BE SPACED A MAXIMUM OF 60 |
| | FEET APART. |
| | |
| | CIVIL WATER SHEET 5 OF 7: THE FIRE HYDRANTS ARE LOCATED |
| | ON A DEAD-END WATER MAIN. PROVIDE LOOPED SYSTEM. |
| | |
| | CIVIL WATER SHEET 3 OF 9: BOTH THE FIRE WATER AND |
| | DOMESTIC WATER ARE SUPPLIED BY A COMMON 4-INCH MAIN. |
| | PROVIDE INDEPENDENT FIRE/DOMESTIC TAPS INTO THE 8-INCH |
| | FEED MAIN. |
| | |
| | CIVIL WATER SHEET 4 OF 9: FIRE HYDRANTS SHALL BE |
| | PROVIDED WITH CLEARANCES OF 7?-6? TO THE FRONT AND |
| | SIDES AND 4? TO THE BACKSIDE. THE PARKING SPACES |
| | ADJACENT TO THE FIRE HYDRANTS APPEAR TO ENCROACH UPON |
| | THE REQUIRED CLEARANCE. |
| | |
| | SHEET LP2: CONFIRM PLUMBAGO LANDSCAPE TO BE LOCATED |
| | OUTSIDE THE 7'-6" CLEAR SPACE RADIUS OF THE NEW FIRE |
| | HYDRANT. |
| | |
| | SHEET A4: PLANS INDICATE BATTERY BACK-UP FOR |
| | ELECTROMAGNETIC LOCK; CONFIRM LOSS OF POWER TO THE |
| | ACCESS CONTROL SYSTEM UNLOCKS THE DOORS IN THE |
| | DIRECTION OF EGRESS. DOORS SHALL BE FAIL SAFE. |
| | |
| | SHEET A4: DOOR MARKER "A" INDICATES AN ELECTROMAGNETIC |
| | LOCK AND AN EXTERIOR KEY OPERATED CYLINDER. INDICATE |
| | HOW THE KEY OPERATED CYLINDER WILL BE UNLOCKED FROM THE |
| | EGRESS SIDE. |
| | NOTE: THE LOCK/LATCH RELEASING MECHANISM ON ALL DOORS |
| | SHALL OPEN THE DOOR WITH NOT MORE THAN ONE RELEASING |
| | OPERATION. |
| | |
| | SHEET A4: LOBBY DOOR "B" MAY BE SUBJECT TO MORE THAN |
| | 100 PERSONS AND WILL NEED TO BE RELEASED BY PANIC |
| | HARDWARE. |
| | |
| | SHEET FP1: DRAWING IS NOT SIGNED/SEALED BY A |
| | PROFESSIONAL ENGINEER. |
| | |
| | SHEET FP1:THE FIRE DEPARTMENT CONNECTION SHALL BE |
| | LOCATED NEAR FIRE DEPARTMENT ACCESS POINT. RECOMMEND A |
| | FREE STANDING CONNECTION NEAR THE NEW FIRE HYDRANT OR A |
| | WALL MOUNTED CONNECTION AT THE NORTHEAST OF THE |
| | BUILDING. |
| | |
| | SHEET FP1: PROVIDE CHAIN WITH LOCK AND TAMPER SWITCHES |
| | FOR SUPERVISING THE BACKFLOW PREVENTER IN THE OPEN |
| | POSITION. |
| | |
| | SHEET FA1: FIRE SPRINKLER FLOW SWITCH SHALL INITIATE A |
| | GENERAL FIRE ALARM CONDITION. |
| | |
| | SHEET FA1: PER LOCAL CODE AMENDMENTS, DUCT SMOKE |
| | DETECTORS SHALL INITIATE A GENERAL FIRE ALARM |
| | CONDITION. |
| | |
| | SHEET FA1: PROVIDE MONITOR MODULES FOR SUPERVISING THE |
| | FIRE SPRINKLER BACKFLOW PREVENTER. |
| | |
| | SHEET FA1: PROVIDE SMOKE DETECTION FOR GYM AREA AND |
| | HALL #6. |
| | |
| | WESLEY JOLIN |
| | WEST PALM BEACH FIRE RESCUE |
| | FIRE & LIFE SAFETY PLAN REVIEW |